Operating instructions

W3G800-GV01-91

`

II 2G Ex db eb ib IIB T3 Gb

IBExU14ATEX1123 X /03

`

Translation of the original operating instructions

54001-4-8670

7. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on the device. Send it to ebm-papst for repair
or replacement.
During maintenance work on the fan, e.g. when cleaning the fan blades,
the fan must be stationary and its electrical circuit must be interrupted and
secured against being switched on again.

;

Wait until the device comes to a stop.

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ When shutting off the device, note Chapter 5.8 Switching off

the device.

→ Wait five minutes after disconnecting the voltage at all

poles before opening the device.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after mains
failure.

Risk of injury
→ When working on the device, switch off the line voltage and

ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ Keep out of the device danger zone.
→ After performing work on the device, remove any tools

used or other objects from the fan air paths.

If the device is out of use for over four months, we recommend
switching it on for at least three hours at full speed to allow any
condensation to evaporate and to move the bearings.

;

Carry out inspections and cleaning as appropriate for the Ex marking
so that no dirt deposits form.

Malfunction/fault

Possible cause

Possible remedy

Impeller not
running smoothly

Imbalance in rotating
parts

Clean the device;
replace if imbalance
persists after
cleaning. Make sure
no weight clips are
moved, damaged or
removed during
cleaning.

Motor not turning

Mechanical blockage

Switch off, isolate
from supply and
remove mechanical
blockage.

Line voltage faulty

Check line voltage,
restore power
supply. Attention! The
error message resets
automatically. Device
restarts automatically
without warning.

Faulty connection

Isolate from supply,
correct connection;
see connection
diagram.

Broken motor winding Replace device

Deficient cooling

Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the line voltage for at
least 25 s and then
switch it on again.
Alternatively, reset
the error message by
applying a control
signal of < 0.5 V to
Din1 or by shorting
Din1 to GND.

Ambient temperature
too high

Reduce the ambient
temperature. Let the
device cool down.
To reset the error
message, switch off
the line voltage for at
least 25 s and then
switch it on again.
Alternatively, reset
the error message by
applying a control
signal of < 0.5 V to
Din1 or by shorting
Din1 to GND.

Impermissible point of
operation (e.g.
excessive load, back
pressure too high)

Correct the operating
point. Let the device
cool down.
To reset the error
message, switch off
the line voltage for at
least 25 s and then
switch it on again.
Alternatively, reset
the error message by
applying a control
signal of < 0.5 V to
Din1 or by shorting
Din1 to GND.

Terminal box
fastening screws
broken while closing

Replace device

In the event of further malfunctions, contact ebm-papst.

7.1 Cleaning

NOTE
Damage to the device during cleaning

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

cleaner.

→ Do not use any acid, alkali or solvent-basedcleaning

agents.

→ Do not use any pointed or sharp-edged objects for cleaning

Item no. 54001-5-9970 · ENU · Change 272968 · Approved 2022-11-23 · Page 16 / 17

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G800-GV01-91

Страница 1: ...ng instructions are available in other languages on our website www ebmpapst com 2 2 SAFETY REGULATIONS AND INFORMATION 2 2 1 Hazard levels for warnings 2 2 2 Staff qualifications 2 2 3 Basic safety r...

Страница 2: ...h the operating instructions Malfunctions and defects that affect safety must always be corrected immediately No modifications additions or conversions are to be made to the device for example changes...

Страница 3: ...d its attachment must always be evaluated in connection with the overall safety concept of the system as a whole 2 8 Emissions WARNING Depending on the installation and operating conditions the sound...

Страница 4: ...rmitted ambient temperature range see Chapter 4 2 Nominal data and Chapter 4 5 Transport and storage conditions Operating the device with all protective devices Using the device only in Zones 1 and 2...

Страница 5: ...max 14 mm tightening torque 6 0 6 Nm standard value depending on cable 5 Terminal box fastening screws M4 x 20 tightening torque 3 5 0 5 Nm 6 Ground connection point M8 functional ground for discharg...

Страница 6: ...in the product drawing Use the fastening components available from ebm papst for assembly At one mounting point the contact washer 4 must also be inserted between the housing and the nut Tighten the...

Страница 7: ...osition Shaft horizontal with cable exit 45 or rotor at bottom rotor at top not permissible Condensation drainage holes On rotor side Mode S1 Motor bearing Ball bearing Technical features Output 10 VD...

Страница 8: ...of safety 4 8 The nameplate Fig 1 Specifications on the nameplate Serial number Designation Explanation YY Year Year e g 11 for production in 2011 WW Week Week calendar week in year of production Six...

Страница 9: ...d to air ducts the connection should be isolated from vibration e g using compensators or similar elements Ensure stress free attachment of the fan to the substructure Check the device for transport d...

Страница 10: ...l indicated on the nameplate see Chapter 5 3 3 Connecting wires to terminals For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth must have a cross...

Страница 11: ...commended stripped lengths in mm inside terminal box for unshielded cables In this illustration all cable glands are used by way of example The illustration may differ from the actual device design Fi...

Страница 12: ...box screw connections and cable glands have been tightened to the specified torque 5 3 3 1 Replacement of cable glands and screw plugs If you would like to replace cable glands or screw plugs for exam...

Страница 13: ...y settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes...

Страница 14: ...put of current motor modulation level motor speed adjustable curve SELV 2 Din 2 Digital input 2 Switching parameter sets 1 2 according to EEPROM setting the valid or used parameter set can be selected...

Страница 15: ...sonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessive...

Страница 16: ...ng cleaning Motor not turning Mechanical blockage Switch off isolate from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message...

Страница 17: ...ery 6 months Fasten cables Cleaning and preventive maintenance Visual inspection At least every 3 months Remove dirt clean device Ball bearings for smooth and noiseless movement free of play acoustic...

Отзывы: