Operating instructions

W3G800-GV01-91

`

II 2G Ex db eb ib IIB T3 Gb

IBExU14ATEX1123 X /03

`

Translation of the original operating instructions

54001-4-8670

Fig. 4: Connecting wires to terminals (example)

There must be no mechanical stress acting between the terminal and the
cable gland. The cable must be relieved of strain.

Fig. 5: Secure the brackets (included in terminal box) for strain relief of
the wires

Fig. 6: Strain relief for shielded wires

The strain relief acts on the cable sheath, eliminating strain on
the leads.

DANGER
Risk of explosion due to poorly sealed terminal box.

The terminal box cover, its seal and the contact surface on the
housing must not be soiled or damaged.
→ Clean the contact surfaces if soiled; heed the section on

cleaning.

→ If the device is damaged, send it to ebm-papst for repair

or replacement.

The terminal box is only properly sealed if the terminal box
screw connections and cable glands have been tightened to the
specified torque.

5.3.3.1 Replacement of cable glands and screw plugs

If you would like to replace cable glands or screw plugs, for example
because they have been lost or become worn out, they must have the
following characteristics.

CAUTION

Required properties for cable glands and screw plugs:- Ex e
approval
- Usage temperature -40°C to 85°C
- Connection thread M20 x 1.5 mm or M25 x 1.5 mm
- Sizing corresponding to cable diameter
- Material: Nickel-plated brass or stainless steel

5.3.4 Cable routing

Water must be prevented from reaching the cable gland along the cable.
To relieve strain on the cables, we recommend fastening the cables at
intervals of 10 cm.

Fans installed lying flat

Make sure the cables are routed in a U-shaped loop.

Fig. 7: Fan installed lying flat, cable routed in a U-shaped loop.

Item no. 54001-5-9970 · ENU · Change 272968 · Approved 2022-11-23 · Page 12 / 17

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G800-GV01-91

Страница 1: ...ng instructions are available in other languages on our website www ebmpapst com 2 2 SAFETY REGULATIONS AND INFORMATION 2 2 1 Hazard levels for warnings 2 2 2 Staff qualifications 2 2 3 Basic safety r...

Страница 2: ...h the operating instructions Malfunctions and defects that affect safety must always be corrected immediately No modifications additions or conversions are to be made to the device for example changes...

Страница 3: ...d its attachment must always be evaluated in connection with the overall safety concept of the system as a whole 2 8 Emissions WARNING Depending on the installation and operating conditions the sound...

Страница 4: ...rmitted ambient temperature range see Chapter 4 2 Nominal data and Chapter 4 5 Transport and storage conditions Operating the device with all protective devices Using the device only in Zones 1 and 2...

Страница 5: ...max 14 mm tightening torque 6 0 6 Nm standard value depending on cable 5 Terminal box fastening screws M4 x 20 tightening torque 3 5 0 5 Nm 6 Ground connection point M8 functional ground for discharg...

Страница 6: ...in the product drawing Use the fastening components available from ebm papst for assembly At one mounting point the contact washer 4 must also be inserted between the housing and the nut Tighten the...

Страница 7: ...osition Shaft horizontal with cable exit 45 or rotor at bottom rotor at top not permissible Condensation drainage holes On rotor side Mode S1 Motor bearing Ball bearing Technical features Output 10 VD...

Страница 8: ...of safety 4 8 The nameplate Fig 1 Specifications on the nameplate Serial number Designation Explanation YY Year Year e g 11 for production in 2011 WW Week Week calendar week in year of production Six...

Страница 9: ...d to air ducts the connection should be isolated from vibration e g using compensators or similar elements Ensure stress free attachment of the fan to the substructure Check the device for transport d...

Страница 10: ...l indicated on the nameplate see Chapter 5 3 3 Connecting wires to terminals For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth must have a cross...

Страница 11: ...commended stripped lengths in mm inside terminal box for unshielded cables In this illustration all cable glands are used by way of example The illustration may differ from the actual device design Fi...

Страница 12: ...box screw connections and cable glands have been tightened to the specified torque 5 3 3 1 Replacement of cable glands and screw plugs If you would like to replace cable glands or screw plugs for exam...

Страница 13: ...y settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes...

Страница 14: ...put of current motor modulation level motor speed adjustable curve SELV 2 Din 2 Digital input 2 Switching parameter sets 1 2 according to EEPROM setting the valid or used parameter set can be selected...

Страница 15: ...sonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessive...

Страница 16: ...ng cleaning Motor not turning Mechanical blockage Switch off isolate from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message...

Страница 17: ...ery 6 months Fasten cables Cleaning and preventive maintenance Visual inspection At least every 3 months Remove dirt clean device Ball bearings for smooth and noiseless movement free of play acoustic...

Отзывы: