Operating instructions

W3G800-GV01-91

`

II 2G Ex db eb ib IIB T3 Gb

IBExU14ATEX1123 X /03

`

Translation of the original operating instructions

54001-4-8670

5.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Explosion hazard

→ To dissipate electrostatic charges, the fan must be grounded

via the grounding point on the fan housing.

→ Operation of the fan without grounding to dissipate

electrostatic charges is not permitted.

NOTE
The minimum permissible temperature for connection of
the cables to the terminals is -35°C.

The terminals may be damaged.
→ Only connect the cables at temperatures above -35°C.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot come into contact with

rotating parts.

→ Only use cables that are designed for the current level

indicated on the nameplate and approved for use in
potentially explosive atmospheres.

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

NOTE
Device malfunctions possible

Route the device's control lines separately from the supply line.
→ Maintain the greatest possible clearance.

Recommendation: clearance > 10 cm (separate cable
routing)

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

5.2.1 Requirements

;

Check whether the data on the nameplate match the connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate; see Chapter 5.3.3 Connecting wires to terminals. For
determining the cross-section, note the sizing criteria according to EN
61800-5-1. The protective earth must have a cross-section equal to or
greater than that of the phase conductor. We recommend the use of
105 °C cables.

;

Only use cables approved for the corresponding ambient temperature.

;

Do not subject the cables to impermissible strain.

;

Establish a safe protective earth connection.

;

Ensure that the degree of protection is maintained. The seals in the
terminal box from ebm-papst have been inspected for suitability.

The motor must be connected in accordance with EN 60079-14.

Ground conductor contact resistance according to EN 61800-5-1

Compliance with the impedance specifications according to EN 61800-5-
1 for the protective earth connection circuit must be verified in the end
application. Depending on the circumstances of installation, it may be
necessary to connect an additional protective earth conductor to the extra
protective earth terminal on the device. The protective earth terminal is
on the housing and has a ground conductor symbol and a bore hole.

5.2.2 Supply connection and fuses

Assignment of supply cable cross-sections and their required fuses (line
protection only, no equipment protection).

Nominal
voltage

Fuse

Automatic
circuit
breaker

Wire
cross-
section

Wire
cross-
section

VDE

UL

VDE

mm²

*AWG

3/PE AC
380-440
VAC

16 A

15 A

C16A

1.5

16

3/PE AC
380-440
VAC

20 A

20 A

C20A

2.5

14

3/PE AC
380-440
VAC

25 A

25 A

C25A

4.0

12

* AWG = American Wire Gauge

5.2.3 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically less than 250 mA.

At the same time, the effective power in this operating state
(operational readiness) is typically < 5 W.

Item no. 54001-5-9970 · ENU · Change 272968 · Approved 2022-11-23 · Page 10 / 17

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G800-GV01-91

Страница 1: ...ng instructions are available in other languages on our website www ebmpapst com 2 2 SAFETY REGULATIONS AND INFORMATION 2 2 1 Hazard levels for warnings 2 2 2 Staff qualifications 2 2 3 Basic safety r...

Страница 2: ...h the operating instructions Malfunctions and defects that affect safety must always be corrected immediately No modifications additions or conversions are to be made to the device for example changes...

Страница 3: ...d its attachment must always be evaluated in connection with the overall safety concept of the system as a whole 2 8 Emissions WARNING Depending on the installation and operating conditions the sound...

Страница 4: ...rmitted ambient temperature range see Chapter 4 2 Nominal data and Chapter 4 5 Transport and storage conditions Operating the device with all protective devices Using the device only in Zones 1 and 2...

Страница 5: ...max 14 mm tightening torque 6 0 6 Nm standard value depending on cable 5 Terminal box fastening screws M4 x 20 tightening torque 3 5 0 5 Nm 6 Ground connection point M8 functional ground for discharg...

Страница 6: ...in the product drawing Use the fastening components available from ebm papst for assembly At one mounting point the contact washer 4 must also be inserted between the housing and the nut Tighten the...

Страница 7: ...osition Shaft horizontal with cable exit 45 or rotor at bottom rotor at top not permissible Condensation drainage holes On rotor side Mode S1 Motor bearing Ball bearing Technical features Output 10 VD...

Страница 8: ...of safety 4 8 The nameplate Fig 1 Specifications on the nameplate Serial number Designation Explanation YY Year Year e g 11 for production in 2011 WW Week Week calendar week in year of production Six...

Страница 9: ...d to air ducts the connection should be isolated from vibration e g using compensators or similar elements Ensure stress free attachment of the fan to the substructure Check the device for transport d...

Страница 10: ...l indicated on the nameplate see Chapter 5 3 3 Connecting wires to terminals For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth must have a cross...

Страница 11: ...commended stripped lengths in mm inside terminal box for unshielded cables In this illustration all cable glands are used by way of example The illustration may differ from the actual device design Fi...

Страница 12: ...box screw connections and cable glands have been tightened to the specified torque 5 3 3 1 Replacement of cable glands and screw plugs If you would like to replace cable glands or screw plugs for exam...

Страница 13: ...y settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes...

Страница 14: ...put of current motor modulation level motor speed adjustable curve SELV 2 Din 2 Digital input 2 Switching parameter sets 1 2 according to EEPROM setting the valid or used parameter set can be selected...

Страница 15: ...sonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessive...

Страница 16: ...ng cleaning Motor not turning Mechanical blockage Switch off isolate from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message...

Страница 17: ...ery 6 months Fasten cables Cleaning and preventive maintenance Visual inspection At least every 3 months Remove dirt clean device Ball bearings for smooth and noiseless movement free of play acoustic...

Отзывы: