54006-4-8670

Regular cleaning of the device prevents imbalance caused by
deposits, for example.

7.2 Safety inspection

NOTE
High-voltage test

The integrated EMC filter has Y capacitors. The tripping current
is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you perform the

legally required high-voltage test. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.

7.3 Maintenance interval

What to check

How to check

How often

What action?

Corrosion

Visual inspection At least every

3 months

When there is
heavy
corrosion that
impairs the
explosion
protection, e.g.
in gap
surfaces,
replace the
device.

Contact
protection
cover for
intactness or
damage

Visual inspection At least every

6 months

Repair or
replacement of
device

Device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement of
device

Fastening the
cables

Visual inspection At least every

6 months

Fasten

Insulation of
cables for
damage

Visual inspection At least every

6 months

Replace wires

Impeller for
wear/deposits/
corrosion and
damage

Visual inspection At least every

6 months

Clean impeller
or replace device

Tightness of
cable gland

Visual inspection At least every

6 months

Retighten,
replace if
damaged

Condensation
drainage holes
for clogging,
where necessary

Visual inspection At least every

6 months

Open holes

Welds for crack
formation

Visual inspection At least every

6 months

Replace device

Cable routing
(fastening)

Visual inspection At least every

6 months

Fasten cables

Cleaning and
preventive
maintenance

Visual inspection At least every

3 months

Remove dirt,
clean device

Ball bearings
for smooth and
noiseless
movement free
of play

acoustic and/or
manual check
by turning rotor
when switched
off, vibration test

At least every
3 months

Replace the
device in the
event of noise,
stiffness or
bearing play.
Have motor
bearings
replaced by
ebm-papst.

Vibration test

See Vibration
test section

At least every
6 months

Cleaning,
repair or
replacement of
device

Check gap
dimensions

See Gap
dimensions
section

At least every
3 months

Replacement of
device

7.4 Vibration check

Regular checks must be made to ensure that the fan is not operated at
impermissibly high vibration levels. On the basis of ISO 14694, the
maximum permissible vibration velocities are specified as follows:

Fan connected to system
with isolation from vibration

Fan connected to system
without isolation from
vibration

Vibration velocity

Vibration velocity

max. 6.3 mm/s

max. 4.5 mm/s

Fig. 9: The vibration velocities are measured in radial direction at the
stator bushing.

The motor bearings are provided with permanent lubrication at the
factory. Experience has shown that under normal operating conditions
the grease therefore only has to be renewed after several years. The
motor must be deactivated in the event of bearing noise. To remedy this,
the motor has to be exchanged or the defective bearings replaced by the
ebm-papst Service department.
A record is to be kept of the routine inspections performed.

Item no. 54006-5-9970 · ENU · Change 93219 · Approved 2018-02-08 · Page 16 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G560-AP23-90

Страница 1: ...instructions are available in other languages on our website www ebmpapst com 2 2 SAFETY REGULATIONS AND INFORMATION 2 2 1 Hazard levels for warnings 2 2 2 Staff qualifications 2 2 3 Basic safety rul...

Страница 2: ...urpose in a safe manner with attention to potential dangers and in accordance with the operating instructions No modifications additions or conversions are to be made to the device for example changes...

Страница 3: ...n and operating conditions the sound pressure level may exceed 70 dB A Risk of noise induced hearing loss Take appropriate technical safety measures Protect operating personnel with appropriate safety...

Страница 4: ...devices Using the device only in Zones 1 and 2 with Ex categories IIA and IIB and temperature classes T1 to T3 Using the device only in stationary systems Using the device only in speed ranges without...

Страница 5: ...er min 10 mm max 14 mm tightening torque 6 0 6 Nm standard value depending on cable 6 Terminal box fastening screws tightening torque 3 5 0 5 Nm 7 Ground connection point M8 functional ground for elec...

Страница 6: ...ng Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Operation and alarm display Input for sensor 0 10 V or 4 20 mA External 24 V input parameter setting Exter...

Страница 7: ...production Six digit number e g 000003 Sequential serial number Ex marking II 2G Ex db eb ib IIB T3 Gb Element Explanation Ex marking according to 2014 34 EU II Equipment group II use above ground no...

Страница 8: ...connection should be isolated from vibration e g using compensators or similar elements Ensure stress free attachment of the fan to the substructure Check the device for transport damage Damaged devi...

Страница 9: ...the terminal box from ebm papst have been inspected for suitability The motor must be connected in accordance with EN 60079 14 Ground conductor contact resistance according to EN 61800 5 1 Compliance...

Страница 10: ...3 Connecting wires to terminals Open the terminal box To do so unscrew the seven screws for tightening torque see Chapter 4 1 Product drawing Take care when opening the terminal box cover Do not dama...

Страница 11: ...box screw connections and cable glands have been tightened to the specified torque 5 3 3 1 Replacement of cable glands and screw plugs If you would like to replace cable glands or screw plugs for exa...

Страница 12: ...y settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 1 Max PWM 100 Min PWM 5 1 Save set value to EEPROM Yes...

Страница 13: ...tput of current motor modulation level motor speed adjustable curve SELV 2 Din 2 Digital input 2 Switching parameter sets 1 2 according to EEPROM setting the valid or used parameter set can be selecte...

Страница 14: ...sonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessive...

Страница 15: ...oved during cleaning Motor not turning Mechanical blockage Switch off isolate from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error...

Страница 16: ...e device Cable routing fastening Visual inspection At least every 6 months Fasten cables Cleaning and preventive maintenance Visual inspection At least every 3 months Remove dirt clean device Ball bea...

Отзывы: