Operating instructions

K3G560-AP23-90

`

II 2G Ex db eb ib IIB T3 Gb

IBExU14ATEX1122 X /04

`

Translation of the original operating instructions

54006-4-8670

5.5 Connection diagram

Drawing preliminary!

Shaded => terminals not used

No.

Conn.

Designation

Function/assignment

1

PE

Ground connection, PE connection

1

L1

Supply connection, power supply 3-phase 380-440 VAC, 50/60 Hz

1

L2

Supply connection, power supply 3-phase 380-440 VAC, 50/60 Hz

1

L3

Supply connection, power supply 3-phase 380-440 VAC, 50/60 Hz

1

HZ

not used (optional: internal heating element)

2

RSA

Bus connection RS485, RSA, MODBUS RTU; double terminal point (SELV)

2

RSB

Bus connection RS485, RSB, MODBUS RTU; double terminal point (SELV)

2

GND

Reference ground for control interface (SELV)

2

Ain1 U

Analog input 1, set value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input Ain1 I;
SELV

2

+10 V

Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof power supply for external devices
(e.g. pot); SELV

2

Ain1 I

Analog input 1, set value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input Ain1 U;
SELV

2

Din 1

Digital input 1: enable electronics,
enable: pin open or applied voltage 5-50 VDC
disable: bridge to GND or applied voltage < 1 VDC
reset function: triggers software reset after a level change to < 1 VDC; SELV

2

Aout

Analog output 0-10 VDC, max. 5 mA, output of current motor modulation level / motor speed
adjustable curve; SELV

2

Din 2

Digital input 2: Switching parameter sets 1/2, according to EEPROM setting, the valid or used parameter set
can be selected via bus or via digital input DIN2.
Parameter set 1: pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage < 1 VDC; SELV

2

Din 3

Digital input 3: Direction of action of integrated controller, according to EEPROM setting, the direction of action
of the integrated controller can be selected as normal/inverse via bus or digital input
Normal: Pin open or applied voltage 5-50 VDC
Inverse: Bridge to GND or applied voltage < 1 VDC; SELV

2

Ain2 U

Analog input 2, measured value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input
Ain2 I; SELV

2

+20 V

Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof power supply for external
devices (e.g. sensors); SELV
or: +24 VDC input for parameter setting via MODBUS without line voltage

2

Ain2 I

Analog input 2, measured value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input
Ain2 U; SELV

2

NO

Status relay, floating status contact; make for failure

2

COM

Status relay, floating status contact, common connection, contact rating 250 VAC / max. 2 A (AC1) / min. 10
mA

2

NC

Status relay; floating status contact, break for failure

Item no. 54006-5-9970 · ENU · Change 93219 · Approved 2018-02-08 · Page 13 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G560-AP23-90

Страница 1: ...instructions are available in other languages on our website www ebmpapst com 2 2 SAFETY REGULATIONS AND INFORMATION 2 2 1 Hazard levels for warnings 2 2 2 Staff qualifications 2 2 3 Basic safety rul...

Страница 2: ...urpose in a safe manner with attention to potential dangers and in accordance with the operating instructions No modifications additions or conversions are to be made to the device for example changes...

Страница 3: ...n and operating conditions the sound pressure level may exceed 70 dB A Risk of noise induced hearing loss Take appropriate technical safety measures Protect operating personnel with appropriate safety...

Страница 4: ...devices Using the device only in Zones 1 and 2 with Ex categories IIA and IIB and temperature classes T1 to T3 Using the device only in stationary systems Using the device only in speed ranges without...

Страница 5: ...er min 10 mm max 14 mm tightening torque 6 0 6 Nm standard value depending on cable 6 Terminal box fastening screws tightening torque 3 5 0 5 Nm 7 Ground connection point M8 functional ground for elec...

Страница 6: ...ng Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Operation and alarm display Input for sensor 0 10 V or 4 20 mA External 24 V input parameter setting Exter...

Страница 7: ...production Six digit number e g 000003 Sequential serial number Ex marking II 2G Ex db eb ib IIB T3 Gb Element Explanation Ex marking according to 2014 34 EU II Equipment group II use above ground no...

Страница 8: ...connection should be isolated from vibration e g using compensators or similar elements Ensure stress free attachment of the fan to the substructure Check the device for transport damage Damaged devi...

Страница 9: ...the terminal box from ebm papst have been inspected for suitability The motor must be connected in accordance with EN 60079 14 Ground conductor contact resistance according to EN 61800 5 1 Compliance...

Страница 10: ...3 Connecting wires to terminals Open the terminal box To do so unscrew the seven screws for tightening torque see Chapter 4 1 Product drawing Take care when opening the terminal box cover Do not dama...

Страница 11: ...box screw connections and cable glands have been tightened to the specified torque 5 3 3 1 Replacement of cable glands and screw plugs If you would like to replace cable glands or screw plugs for exa...

Страница 12: ...y settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 1 Max PWM 100 Min PWM 5 1 Save set value to EEPROM Yes...

Страница 13: ...tput of current motor modulation level motor speed adjustable curve SELV 2 Din 2 Digital input 2 Switching parameter sets 1 2 according to EEPROM setting the valid or used parameter set can be selecte...

Страница 14: ...sonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessive...

Страница 15: ...oved during cleaning Motor not turning Mechanical blockage Switch off isolate from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error...

Страница 16: ...e device Cable routing fastening Visual inspection At least every 6 months Fasten cables Cleaning and preventive maintenance Visual inspection At least every 3 months Remove dirt clean device Ball bea...

Отзывы: