background image

G1G170-AB05-20

 

Operating instructions 

 
 
 

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE

 

CAUSES AND REMEDIES

 

Do not perform any repairs on your device. Return the device to ebm- 
papst for repair or replacement. 

WARNING

 

Terminals and connections have voltage even with a

 

unit that is shut off

 

Electric shock 

 Wait five minutes after disconnecting the voltage at all poles 

before opening the device. 

CAUTION

 

 
 
 

Mains supply 
voltage faulty 

 
 
 

Faulty connection 

 
 

Thermal overload 
protector responded 

 
 
 

Check mains supply 

voltage, 

restore power 
supply, 
apply control signal. 
De-energise, correct 
connection, see 
connection diagram. 

Allow motor to cool 

off, locate and rectify 
cause of error, if 
necessary cancel 
restart lock-out 

If the control signal of a blower that is connected to the

 

power system is removed, the motor can restart

 

automatically.

 

Danger of injury 

 When working on the blower, switch off the mains supply 

voltage and secure it from being switched on again. 

 Wait until the device stops. 

CAUTION

 

Electrical load after device is switched off

 

Electric shock in case of contact 

 Wait for five minutes after disconnecting the voltage at all 

poles before touching the unit. 

CAUTION

 

If control voltage is applied or a speed setpoint is stored,

 

the motor automatically restarts, e.g. after a power failure.

 

Danger of injury 

 Keep out of the danger zone of the device. 

 When working on the device, switch off the mains 

supply voltage and secure the latter from being switched on 

Overtemperature of

 

electronics/motor

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Deflagration

 

Insufficient cooling 

Improve cooling. Let 
the device cool 

down. 

To reset the error 
message, switch off 
the mains supply 
voltage for a min. of 

25 s and switch it on 

again. 

Ambient temperature 

Reduce the ambient 

too high 

temperature. 

Reset by reducing 
control input to 0. 

Unacceptable 

Correct the operating 

operating point 

point. Let the device 
cool down. 

Leakage of the 

Check for leaks; 

handled air/gas 

replace blower if not 

mixture 

properly sealed 

again. 

 Wait until the device stops. 

 After working on the device, remove any used tools or 

other objects from the device. 

If the blower remains out of use for some time, e.g. when in 
storage, we recommend switching the blower on for at least 2 
hours to allow any condensate to evaporate and to move the 

bearings. 

If you have any other problems, contact ebm-papst. 

 
 

6.1 Cleaning

 

NOTE

 

The device does not need to be cleaned. 

6.2 Safety test

 

Malfunction/error

 

Possible cause

 

Impeller running

 

Imbalance in rotating 

roughly

 parts 

Possible remedy

 

Clean the device; if 
imbalance is still 
evident after 
cleaning, replace the 

device. 

If you have 
attached any weight 
clips during cleaning, 

make sure to 
remove them 
afterwards. 

NOTE

 

High-voltage test

 

The integrated EMC filter contains Y capacitors. Therefore, the 
trigger current is exceeded when AC testing voltage is applied. 

 Test the device with DC voltage when you carry out the 

high-voltage test required by law. The voltage to be used 
corresponds to the peak value of the AC voltage required by 
the standard. 

What has to

 

How to test?

 

Frequency

 

Which

 

be tested?

 

measure?

 

Motor does not turn

 

Mechanical blockage 

Switch off, de- 

energise, and 

remove mechanical 

blockage. 

 
 
 
 

Item no.: 50103-5-9970 · Revision: 70943 · Print-out: 2012-04-11 · Y. Uhlmann (VM-TDO) · Page 11 / 12 

ebm-papst Mulfingen GmbH & Co. KG · Bachm

ь

hle 2 · D-74673 Mulfingen · Phone +49 7938 81-0 · Fax +49 7938 81-110 · [email protected] · www.ebmpapst.com 

T

ranslation of

 the 

or

iginal oper

ating instr

uctions

Содержание G1G170-AB05-20

Страница 1: ...rdous situations and important safety regulations DANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury Compliance with the measures is mandato...

Страница 2: ...r open the blower WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewel...

Страница 3: ...ith the permitted ambient temperature see chapter 3 5 Transport and storage conditions and chapter Only using the device in stationary systems Installing the device into an overall system for moving a...

Страница 4: ...ating instructions Item no 50103 5 9970 Revision 70943 Print out 2012 04 11 Y Uhlmann VM TDO Page 4 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 7938 81 0 Fax 49 7938 81 11...

Страница 5: ...male connector No 926 884 1 L N PE 5 pole strip mating connector not included in delivery Molex No 39 01 4050 female connector Molex No 39 00 0059 Speed monitoring Not assigned PWM input Bleeder conne...

Страница 6: ...tomer specs cu customer unit Subject to alterations 3 3 Technical description Mass 4 35 kg Size 170 mm Surface of rotor Coated in black Material of protective Polyflam RPP 374 ND CS1 UL 97 V0 cover Ma...

Страница 7: ...ided Before working on the electrical connection the connections to the mains supply and PE must be shorted using an all pole disconnecting switch When working on the device you must switch off the sy...

Страница 8: ...on the device you must switch off the system machine in which the device is installed and secure it from being switched on again Check the PIN assignment of your connector Connect the panel connector...

Страница 9: ...ing output connection monitoring circuit output 3 pulses per revolution current source 1 mA Not assigned PWM 2 6 kHz control input PWM on n 100 PWM low n 0 GND Connection for control interface Item no...

Страница 10: ...to the PWM control input if you are using the PWM control input Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 7 Switching off the device Switching off...

Страница 11: ...s supply voltage for a min of 25 s and switch it on again Ambient temperature Reduce the ambient too high temperature Reset by reducing control input to 0 Unacceptable Correct the operating operating...

Страница 12: ...pection At least every 6 months Visual inspection At least every 6 months Visual inspection At least every 6 months Repair or replacement of the device Replacement of the device Fasten Fasten Replace...

Страница 13: ...Translation of the original operating instructions...