6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES
Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.
WARNING
Terminals and connections have voltage even with a
unit that is shut off
Electric shock
→
Wait five minutes after disconnecting the voltage at all poles
before opening the device.
CAUTION
Mains supply
voltage faulty
Faulty connection
Thermal overload
protector responded
Check mains supply
voltage,
restore power
supply,
apply control signal.
De-energise, correct
connection, see
connection diagram.
Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out
If the control signal of a blower that is connected to the
power system is removed, the motor can restart
automatically.
Danger of injury
→
When working on the blower, switch off the mains supply
voltage and secure it from being switched on again.
→
Wait until the device stops.
CAUTION
Electrical load after device is switched off
Electric shock in case of contact
→
Wait for five minutes after disconnecting the voltage at all
poles before touching the unit.
CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.
Danger of injury
→
Keep out of the danger zone of the device.
→
When working on the device, switch off the mains
supply voltage and secure the latter from being switched on
Overtemperature of
electronics/motor
Deflagration
Insufficient cooling
Improve cooling. Let
the device cool
down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Ambient temperature
Reduce the ambient
too high
temperature.
Reset by reducing
control input to 0.
Unacceptable
Correct the operating
operating point
point. Let the device
cool down.
Leakage of the
Check for leaks;
handled air/gas
replace blower if not
mixture
properly sealed
again.
→
Wait until the device stops.
→
After working on the device, remove any used tools or
other objects from the device.
If the blower remains out of use for some time, e.g. when in
storage, we recommend switching the blower on for at least 2
hours to allow any condensate to evaporate and to move the
bearings.
If you have any other problems, contact ebm-papst.
6.1 Cleaning
NOTE
The device does not need to be cleaned.
6.2 Safety test
Malfunction/error
Possible cause
Impeller running
Imbalance in rotating
roughly
parts
Possible remedy
Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.
NOTE
High-voltage test
The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→
Test the device with DC voltage when you carry out the
high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.
What has to
How to test?
Frequency
Which
be tested?
measure?
Motor does not turn
Mechanical blockage
Switch off, de-
energise, and
remove mechanical
blockage.