damaging body parts. Shields must therefore be established on both the suction and return sides in accordance 

with ISO 13857. 

4.2  Electrical connection 

35 

DANGER 

Voltage on the device 

Electric shock 

Always connect a protective earth first 

Check the protective earth 

36 

DANGER 

Electrical charge (>50 

μ

C) between phase conductor and protective earth connection after switching off supply

 

with multiple devices connected in parallel. 

Electric shock, risk of injury 

Ensure sufficient protection against accidental contact. Before working on the electrical circuitry, short the 

supply and PE connections. 

 

37  CAUTION 

Voltage 

The fan is a built-in component and has no disconnecting switch. 

Only connect the fan to circuits that can be switched off with an all-pole disconnection switch. 

When working on the fan, secure the system/machine in which the fan is installed so as to prevent it from being 

switched back on. 

 

38  NOTE 

Electrical noise and consequent malfunction. 

Provide a gap between the supply cable and the control cable when installing these in the application. 

Provide adequate distance. 

Recommendation: distance> 10 cm (separate wiring). 

 

 

39  NOTE 

Water ingress into wires or cables. 

Water ingress at the customer end of the cable can damage the device. 

Make sure the end of the cable is connected in a dry environment. 

 

40  Only connect the fan to circuits that can be switched off with an all-pole disconnection switch. 

 

4.3  Requirements 

41  Check whether the information on the nameplate matches the connection data. 

Before connection the device, make sure the power supply matches the device voltage. 

Only use cables designed for the current level indicated on the nameplate.

 

4.4  RCD 

 If your system requires the use of an FI relay, it is only permitted to use FI relays that are sensitive to all types 

of current (type B or B +). Personal protection is not possible with FI relays when operating the unit, as is the 

case with frequency inverters. When connecting the unit voltage supply, pulse-shaped charging currents from 

the capacitors in the integrated EMC filter can cause the activation of delayed release FI relays. We recommend 

fault current switches with a triggering threshold of 300 mA and delayed release (super-resistant, characteristic 

K). 

 

 

Содержание BoxFan BF700S-355RT01I2

Страница 1: ...akes it resistant to various climate impacts Inside the box the fan is mounted on a warm galvanized sheet metal plate and this is accessed by removing the inspection hatch The fan itself is an EC fan...

Страница 2: ...surface 5 1 10 Storage 5 1 11 Disposal 5 1 12 Transport 5 2 INTENDED USE 5 3 TECHNICAL DATA 6 3 1 Product drawing 6 3 2 Nominal Data 7 3 3 Technical description 8 3 4 Mounting data 8 3 5 Electromagnet...

Страница 3: ...TION Indicates a potentially hazardous situation which can result in minor or moderate injury or damage to property if the specified actions are not taken 4 NOTE A potentially harmful situation can oc...

Страница 4: ...free blowing or free suctioning and is not connected to ducts The protective net must be able to withstand the kinetic energy of an impeller part The unit is a built in component You the owner is res...

Страница 5: ...he longest possible service life The unit must be stored in the temperature range 40o C to 80o C Avoid shocks and bumps When storing or installing the product must be positioned so that it cannot func...

Страница 6: ...under this application 24 Moving air contaminated by dust e g extraction of sawdust Operation of the unit close to combustible materials or components Operation of the device in an explosive atmosphe...

Страница 7: ...x static pressure 880 Pa 1 Nominal data in working point with max load at 230 VAC 26 Additional data PFC Passive LwA Sound effect 87 dB A 2 LpA Sound pressure at 1 m 76 dB A 2 LpA Sound pressure at 3...

Страница 8: ...cordance with the rules of ISO 14118 31 Any emergency stop functions must meet the requirements of ISO 13850 3 5 Electromagnetic compatibility 32 EMC emission EN 61000 6 3 EMC Immunity EN 6100 6 2 Har...

Страница 9: ...e a gap between the supply cable and the control cable when installing these in the application Provide adequate distance Recommendation distance 10 cm separate wiring 39 NOTE Water ingress into wires...