5.3  Troubleshooting 

 

49  The integrated protection features cause the motor to shut down automatically in the case of errors described 

below: 

 

Malfunction

 

Possible cause

 

Possible solution

 

Motor not running 

Mechanical blocking 

Turn off, disconnect, and remove the 

mechanical blockage. Reset by 

disconnecting the power supply for at 

least 20 seconds after the motor comes 

to a stand-still. 

Voltage failure 

Check voltage 

Restore supply 

Connect control signal 

Connection error 

Correct connection. See connection 

diagram. Reset by disconnecting the 

power supply for at least 20 seconds 

after the motor comes to a stand-still 

Thermal overload 

Protection active 

Let the unit cool off. Reset by 

disconnecting the power supply for at 

least 20 seconds after the motor comes 

to a stand-still 

High electronic temp 

Insufficient cooling 

Improve cooling if possible. Reset by 

disconnecting the power supply for at 

least 20 seconds after the motor comes 

to a stand-still

 

High operating temperature 

Lower temp. if possible 

Reset by reducing control signal to 0 

VDC 

Impeller runs unevenly 

Imbalance in rotating parts 

Clean the unit and balance it properly. 

If imbalance Is still present, the unit is 

replaced. 

 

 

50  The machine cannot be repaired. Only original part is the fan. 

Therefore, return the unit to ebm-papst for repair or replacement. 

 

51 

WARNING 

 

Terminals and connections have voltage even when the device is turned off. 

Electrical shock. 

Wait for 5 minutes after disconnection all connections before touching the unit. 

 

52 

WARNING 

The machine is equipped with several electronic systems designed to protect the motor from overheating. 

These systems do NOT protect against accidental start. For manual intervention, service and repair switch must 

therefore be used. 

 

53 

ATTENTION 

If the control signal is connected or a setpoint is stored, the motor will automatically restart, e.g. after a power 

failure. Risk of injury. 

Stay outside the unit’s danger zone. 

When working on the unit, the supply voltage must be disconnected and it must be ensured that it does not 

connect again. 

Wait for the unit to stop. 

 

54  If the unit has not been used for an extended period of time, we recommend turning on the unit at least 2 hours 

before using it to remove any condensate, as well as moving the bearings. 

Содержание BoxFan BF700S-355RT01I2

Страница 1: ...akes it resistant to various climate impacts Inside the box the fan is mounted on a warm galvanized sheet metal plate and this is accessed by removing the inspection hatch The fan itself is an EC fan...

Страница 2: ...surface 5 1 10 Storage 5 1 11 Disposal 5 1 12 Transport 5 2 INTENDED USE 5 3 TECHNICAL DATA 6 3 1 Product drawing 6 3 2 Nominal Data 7 3 3 Technical description 8 3 4 Mounting data 8 3 5 Electromagnet...

Страница 3: ...TION Indicates a potentially hazardous situation which can result in minor or moderate injury or damage to property if the specified actions are not taken 4 NOTE A potentially harmful situation can oc...

Страница 4: ...free blowing or free suctioning and is not connected to ducts The protective net must be able to withstand the kinetic energy of an impeller part The unit is a built in component You the owner is res...

Страница 5: ...he longest possible service life The unit must be stored in the temperature range 40o C to 80o C Avoid shocks and bumps When storing or installing the product must be positioned so that it cannot func...

Страница 6: ...under this application 24 Moving air contaminated by dust e g extraction of sawdust Operation of the unit close to combustible materials or components Operation of the device in an explosive atmosphe...

Страница 7: ...x static pressure 880 Pa 1 Nominal data in working point with max load at 230 VAC 26 Additional data PFC Passive LwA Sound effect 87 dB A 2 LpA Sound pressure at 1 m 76 dB A 2 LpA Sound pressure at 3...

Страница 8: ...cordance with the rules of ISO 14118 31 Any emergency stop functions must meet the requirements of ISO 13850 3 5 Electromagnetic compatibility 32 EMC emission EN 61000 6 3 EMC Immunity EN 6100 6 2 Har...

Страница 9: ...e a gap between the supply cable and the control cable when installing these in the application Provide adequate distance Recommendation distance 10 cm separate wiring 39 NOTE Water ingress into wires...

Страница 10: ...asic insulation on supply side and reinforced insulation on control interface side 1 7 COM White 2 Status relay floating status contact common connection contact rating 250 VAC 2A AC1 min 10 mA basic...

Страница 11: ...ominal supply voltage Start the device by changing the input signal 4 8 Switching off the device 46 Switching off the device during operation Switch off the device via the control input to protect it...

Страница 12: ...Lower temp if possible Reset by reducing control signal to 0 VDC Impeller runs unevenly Imbalance in rotating parts Clean the unit and balance it properly If imbalance Is still present the unit is re...

Отзывы: