4.6  Checking connections 

43  Ensure isolation from supply (all phases). 

Make sure a restart is impossible. 

Check the cables for proper fit. 

4.7  Switching on the device 

WARNING 

44  Understanding the product. 

Before using the product or after delivery or moving, make sure that the operator is familiar with these operating 

instructions and is familiar with the procedures for use, control and inspection of the machine. 

 

45  Hot motor housing,. 

Risk of fire.. 

Ensure that no combustible or flammable materials are located close to the fan. 

Before switching on, check the device for visible external damage and make sure the protective devices are 

functional. 

Apply the nominal supply voltage. 

Start the device by changing the input signal. 

4.8  Switching off the device 

46  Switching off the device during operation: 

Switch off the device via the control input to protect it. 

Do not switch the motor (e.g. in cyclic operation) on and off via power supply. 

Switching off the device for maintenance: 

Disconnect the device from the power supply. 

 

 

 

 

-//- 

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE CAUSES 

AND REMEDIES 

5.1  Cleaning 

47  The fan is maintenance-free.  

Impeller cleaning is recommended only if subsequent proper balancing is performed. 

NOTE 

If the unit is damaged during cleaning, malfunctions are possible 

Do not clean the unit using water jets or high pressure washers. 

5.2  Safety inspection 

48  Every 6 months the following should be testes visually: 

Do all protective parts fit properly? 

Is the product damaged? 

Is the product fitted correctly? 

Are all cables fitted correctly? 

Is the product earthing properly fitted? 

Is the cable insulation defective? 

 

 

Содержание BoxFan BF700S-355RT01I2

Страница 1: ...akes it resistant to various climate impacts Inside the box the fan is mounted on a warm galvanized sheet metal plate and this is accessed by removing the inspection hatch The fan itself is an EC fan...

Страница 2: ...surface 5 1 10 Storage 5 1 11 Disposal 5 1 12 Transport 5 2 INTENDED USE 5 3 TECHNICAL DATA 6 3 1 Product drawing 6 3 2 Nominal Data 7 3 3 Technical description 8 3 4 Mounting data 8 3 5 Electromagnet...

Страница 3: ...TION Indicates a potentially hazardous situation which can result in minor or moderate injury or damage to property if the specified actions are not taken 4 NOTE A potentially harmful situation can oc...

Страница 4: ...free blowing or free suctioning and is not connected to ducts The protective net must be able to withstand the kinetic energy of an impeller part The unit is a built in component You the owner is res...

Страница 5: ...he longest possible service life The unit must be stored in the temperature range 40o C to 80o C Avoid shocks and bumps When storing or installing the product must be positioned so that it cannot func...

Страница 6: ...under this application 24 Moving air contaminated by dust e g extraction of sawdust Operation of the unit close to combustible materials or components Operation of the device in an explosive atmosphe...

Страница 7: ...x static pressure 880 Pa 1 Nominal data in working point with max load at 230 VAC 26 Additional data PFC Passive LwA Sound effect 87 dB A 2 LpA Sound pressure at 1 m 76 dB A 2 LpA Sound pressure at 3...

Страница 8: ...cordance with the rules of ISO 14118 31 Any emergency stop functions must meet the requirements of ISO 13850 3 5 Electromagnetic compatibility 32 EMC emission EN 61000 6 3 EMC Immunity EN 6100 6 2 Har...

Страница 9: ...e a gap between the supply cable and the control cable when installing these in the application Provide adequate distance Recommendation distance 10 cm separate wiring 39 NOTE Water ingress into wires...

Страница 10: ...asic insulation on supply side and reinforced insulation on control interface side 1 7 COM White 2 Status relay floating status contact common connection contact rating 250 VAC 2A AC1 min 10 mA basic...

Страница 11: ...ominal supply voltage Start the device by changing the input signal 4 8 Switching off the device 46 Switching off the device during operation Switch off the device via the control input to protect it...

Страница 12: ...Lower temp if possible Reset by reducing control signal to 0 VDC Impeller runs unevenly Imbalance in rotating parts Clean the unit and balance it properly If imbalance Is still present the unit is re...

Отзывы: