35
5.2
OPERATION
The pump can operate in 5 different modes. We can set the pump in the most appropriate mode, depending on
the system where the pump operates.
The pump modes:
•
Automatic mode (factory default),
•
Proportional pressure,
•
Constant pressure,
•
Constant speed,
•
Combined mode (all mode indicators are off) – only available on Ego 2 slim and Module C.
Automatic mode
In automatic mode the pump automatically sets the operating pressure, depending on the hydraulic
system. By doing so, the pump finds the optimal operating position.
This mode is recommended in most systems.
The parameters cannot be set; they can only be scrolled through.
Proportional pressure
The pump maintains the pressure with relation to the current flow. The
pressure is equal to the set pressure (Hset on the drawing) at MAX IIimum power;
at 0 flow it is equal to HQ % (default 50%, HQ % can be set on the pump webpage)
of the set pressure. In between, the pressure changes linearly, relative to the flow.
In regulated mode we can only set the pump pressure (Hset on the drawing). We
can only scroll through the other parameters.
Constant pressure
The pump maintains the currently set pressure (Hset on the drawing), from 0 flow
to MAX IIimum power, where the pressure begins to drop.
At constant pressure, we can only set the pressure (Hset on the drawing) which the pump
will maintain. We can only scroll through the other parameters.
Constant speed
The pump operates with the currently set speed (RPMset on the drawing).
In the unregulated mode, we can only set the speed at which the pump will operate. We
can only scroll through the other parameters.
Combined mode
Multiple limits can be set only over the web interface. None of the other modes are on.
Night mode
When the pump is operating in night mode, it automaticly switches between the current mode and night
mode. Switch occurs based on the temperature of the medium. While in night mode its icon is turned on and the
pump operates in chosen mode. If the pump senses drop in temperature of the medium for 15 -20 °C (in time
frame of 2 hours), icon starts to blink and the pump switches to night mode. When the temperature of the
medium rises, blinking stops and the pump goes back to previously chosen operation mode.
Night mode can only work in compliment to other modes and is not a mode that can run by itself.
Max.
Min.
Hset
H
Q
Max
.
H
Q
Min.
RPM
set
Ma
x
Min
H
Q
Hset*HQ%
Hset
Содержание Ego 2 slim
Страница 91: ...91 EGO 2 TC SLIM 32 120...
Страница 92: ...92 EGO 2 TC SLIM 40 40...
Страница 93: ...93 EGO 2 TC SLIM 40 80...
Страница 94: ...94 EGO 2 TC SLIM 40 120...
Страница 95: ...95 EGO 2 TC SLIM 40 180...
Страница 96: ...96 EGO 2 TC SLIM 50 40...
Страница 97: ...97 EGO 2 TC SLIM 50 80...
Страница 98: ...98 EGO 2 TC SLIM 50 120...
Страница 99: ...99 EGO 2 TC SLIM 50 180...
Страница 100: ...100 EGO 2 TC SLIM 65 40...
Страница 101: ...101 EGO 2 TC SLIM 65 80...
Страница 102: ...102 EGO 2 TC SLIM 65 120...
Страница 103: ...103 EGO 2 TC SLIM 65 180...
Страница 104: ...104 EGO 2 TC SLIM 80 40...
Страница 105: ...105 EGO 2 TC SLIM 80 80...
Страница 106: ...106 EGO 2 TC SLIM 80 120...
Страница 107: ...107 EGO 2 TC SLIM 80 180...
Страница 108: ...108 EGO 2 TC SLIM 100 40...
Страница 109: ...109 EGO 2 TC SLIM 100 80...
Страница 110: ...110 EGO 2 TC SLIM 100 120...
Страница 111: ...111 EGO 2 TC SLIM 100 180...
Страница 112: ...112 SLIKE PICTURES BILDER IMMAGINI KUVAT SLIKE 1 A...
Страница 113: ...113 2...
Страница 114: ...114 3...
Страница 115: ...115 4 5 90...
Страница 116: ...116 Ego 2 TC slim 200W Ego 2 TC slim 850W 6...
Страница 117: ......