8
14 Installation of ZB-S 26, 18, 18C6, 10C, 10C6 in the EBR-S-2050 electrical service room
Manual: ZB-S central battery system in electrical service rooms EBR-S
40071860238 (C) November 2017 www.ceag.de
15 Technical data
Type
ZB-S/26
ZB-S/18
ZB-S/LAD
Battery cabinet
ZB-S/10C
ZB-C/26C6 ZB-S/18C6
ZB-S/10C6
ZB-S/18C3
ZB-S/10C3
ZB-S/2C3
CG 200
CG 100
Electrical service room including cable barrier
and ventilation barrier.
EBR-S-2050
EBR-S-2050
EBR-S-2050
EBR-S-2050
EBR-S-2050
Project-specific planning on-site is necessary with oversize.
EBR-S-2050
EBR-S-2050
EBR-S-1800
EBR-S-1800
EBR-S-1800
EBR-S-1800
EBR-S-1800
CEAG part number
40036071113
40036071113
40036071113
40036071113
40036071113
40036071113
40036071113
40036071111
40036071111
40036071111
40036071111
40036071111
Electrical service room including cable barrier
and ventilation barrier. Self-assembly
EBR-S-2050
EBR-S-2050
EBR-S-2050
EBR-S-2050
EBR-S-2050
EBR-S-2050
EBR-S-2050
EBR-S-1800
EBR-S-1800
EBR-S-1800
EBR-S-1800
EBR-S-1800
CEAG part number
40036071112
40036071112
40036071112
40036071112
40036071112
40036071112
40036071112
40036071110
40036071110
40036071110
40036071110
40036071110
Installation of the system in an assembled
room is possible at a later date
no
no
no
no
no
no
no
yes
yes
yes
yes
yes
Max. airflow [m³/h] acc to. EN50272-2
for boost charge*
3.86
2.32
3.86
3.86
1.01
1.01
0.60
0.51
0.22
Max. heat loss rate [W]*
800
700
600
13
300
400
350
250
200
150
200
80
No. of KRS 125 cable sealings for 26 cables
3 x 2.5 mm² or 10 cables at 3 x 25/16 mm²
4
4
4
4
4
4
4
2
2
2
2
2
Max. no. of 2.5 mm² cables
78
78
8
-
78
78
78
26
26
26
26
26
Max. no. of 25 mm² cables
10
10
10
2
10
10
10
10
10
10
10
10
Dimensions
[H without stand/H with standxWxD; mm]
2417/2501x1144x736 2417/2501x1144x736 2417/2501x1144x736 2417/2501x1144x736
2417/2501x1144x736
2417/2501x1144x736 2417/2501x1144x736 2262/2346x894x586 2262/2346x894x586 2262/2346x894x586 2262/2346x894x586 2262/2346x894x586
Weight (approx.) room/system [kg]
692/180
692/170
692/170
692/170**
692/155
692/205
692/200
459/120
459/115
459/50
459/110
459/35
Accessories
Maximum number of supplementary KRS 125
cable sealings. Max. 26 cables per cable sealing
3 x 2.5 mm² or 10 cables at 3 x 25/16 mm²
(see figure on page 5)
6
6
6
6
6
6
6
4
4
4
4
4
Plinth with plinth panel, width 1060 mm,
H = 84 mm
EBR-S-2050-SO
EBR-S-2050-SO
EBR-S-2050-SO
EBR-S-2050-SO
EBR-S-2050-SO
EBR-S-2050-SO
EBR-S-2050-SO
-
-
-
-
-
CEAG part number
40036071115
40036071115
40036071115
40036071115
40036071115
40036071115
40036071115
-
-
-
-
-
Plinth with plinth panel, width 810 mm
H = 84 mm
-
-
-
-
-
-
-
EBR-S-1800-SO
EBR-S-1800-SO
EBR-S-1800-SO
EBR-S-1800-SO
EBR-S-1800-SO
CEAG part number
-
-
-
-
-
-
-
40036071114
40036071114
40036071114
40036071114
40036071114
Stop rail, cable infeed incl. fixing material
40071361160
40071361160
40071361160
-
40071361160
40071361161
40071361161
-
-
-
-
-
Mounting plinth for wall cabinets
-
-
-
-
-
-
-
-
-
40071360410
-
40071360410
Door stop, left
No additional costs but 6 weeks of delivery time.
No additional costs but 6 weeks of delivery time.
O
* Ventilation for the battery charge
and
heat dissipation must be provided.
** Without batteries
14 Installation of ZB-S 26, 18, 18C6, 10C, 10C6
in the EBR-S-2050 electrical service room
1. Align the system and screw-fasten to the rear wall of
the room.
CAUTION
Holes must be pre-drilled for fastening screws into the
fire protection material. Drill hole depth: max. 25 mm,
screw length: max. 25 mm.
2. Set up the technical ventilation (see the installation and
operating instructions ELECTRICAL SERVICE ROOM
PRIORACK-Elt EBR)
3. Disassemble the roof plate of the ZB-S. Mount the
cable interception system (see the drawing).
4. Feed in the cables.
5. Connect the system in accordance with the CEAG ZB-S
instructions and carry out commissioning of the system.
ZB-S 26 and ZB-S 18 in
EBR-S-2050
ZB-S 18C6 and ZB-S 10C, 10C6
in EBR-S-2050