5.3.3
Power supply
The device is provided with an internal fuse and is protected against polarity reversal. The functional
earthing terminal is connected to both the housing and the 0 V terminal. The device power supply is
not
electrically isolated.
The device requires a 24 VDC power supply from an AC/DC converter with safe isolation (SELV). For
other power supply requirements see Chapter 9.5.1 Power supply,
64.
SELV (safety extra low voltage):
Circuit in which no dangerous voltage is present, even in the event of a single fault.
Wiring
Phoenix Contact MSTB 2.5/3-ST-5.08 connector, Phoenix order no. 1757022 is supplied with the
device.
Tab. 7 Assignment of connector
The following must be observed when the connector wiring is prepared:
Tab. 8 Preparing the wiring of the connector
Fig. 7 Power supply interface
Fig. 8 Phoenix Contact MSTB 2.5/3-ST-5.08 connector (view from the wiring side)
Connection
Assignment
+24 VDC
+24 VDC power supply
Functional earthing connected to housing.
Does not have to be connected.
This connection can be used as protective earthing connection if the
mounting environment requires this.
0 V
0 V power supply (connected to
)
Preparing the wiring of the connector
Terminal type
Pluggable screw terminal
Cross-section
min. 0.75 mm
2
/ max. 2.5 mm
2
(lead or wire)
min. AWG18 / max. AWG12
Stripping length
7 mm
Max. tightening torque
0.6…0.8 Nm / 5…7 Lb. In.
0 V
+24 VDC
Содержание XV-152 Series
Страница 1: ...Operating Instructions 12 2011 MN04802006Z EN XV 152 MICRO PANEL...
Страница 18: ...3 Safety regulations 3 4 Device related hazards 18 MICRO PANEL XV 152 12 2011 MN04802006Z EN www eaton com...
Страница 52: ...6 Operation 6 4 Inserting and removing an SD card 52 MICRO PANEL XV 152 12 2011 MN04802006Z EN www eaton com...
Страница 70: ...9 Technical data 9 9 Ambient conditions 70 MICRO PANEL XV 152 12 2011 MN04802006Z EN www eaton com...