3. Lock #1: No key “KU” is present and key “KB” is held captive
(see Figure 23).
otee:
N
Initially, key “KU” is delivered locked in a Utility lockbox.
Figure 23. Key KB in Lock #1 without key KU.
4. Lock #2: No key “KB” is present and key “KC” is held captive
(see Figure 24).
Figure 24. Key KC in Lock #2 without key KB.
5. Lock #3: No key “KC” is present and the lock pin is extended
locking the slide handles in the extended position so the 38 kV
SEG&TD cannot be inserted or removed from the switchgear
compartment (see Figure 25).
Figure 25. No key in Lock #3 and lock pin extended to lock the
slide handles.
6. Lock #4: No key “KB”’ is present and key “KD” is held captive
(see Figure 26).
Figure 26. Key KD in Lock #4 without key KB.
7. Lock #5: No key “KD” is present and the lock pin is extended
locking the Test Port Shutter in the “Closed” position (see
Figure 27).