23
Instruction Booklet
IB131024EN
Effective November 2017
38 kV Type VCPW-HD Simple Electrical
Ground & Test Device (SEG&TD) lower
terminal instruction booklet
EATON
www.eaton.com
NOTICE
THE CIRCUIT BREAKER INCLUDES ALL NECESSARY INTERLOCKS. FOR
DETAILED INFORMATION PERTAINING TO INDIVIDUAL CIRCUIT BREAKER
INTERLOCKS, REFER TO SECTION 4-9. STRUCTURE MOUNTED POSITIVE
GUIDANCE RAILS INTERFACE WITH THE CIRCUIT BREAKER ALIGNMENT
ROLLERS TO INSURE PROPER PRIMARY CONNECTIONS.
Figure 4-3. VCPW-HD Cell slots for Breaker Shoot Bolt Pin
insertion for DISCONNECT and TEST position.
Figure 4-4. VCPW-HD Shoot Bolt Handles must be pulled and
held inward when inserting breaker into the DISCONNECT
and TEST positions. Be sure the handles return to the out-
ward position when the breaker is placed in the TEST posi-
tion or breaker will not be able to be racked in. Breaker can-
not be racked when in the DISCONNECT position.
Figure 4-5. VCPW-HD Breaker insertion. Push in circuit break-
er to the DISCONNECT position shown. Notee: You cannot
rack the breaker in this position.
Figure 4-6 VCPW-HD Breaker insertion. With Shoot Bolt
Handles pulled and held inward, push in circuit breaker into
the TEST position. Be sure the handles return to the outward
position shown or breaker will not be able to be racked in.
Figure 4-7. VCPW-HD Breaker insertion. Use Levering tool to
rack breaker in to the CONNECT Position. (Levering com-
pleted, shown above).