16
Instruction Booklet
IB131024EN
Effective November 2017
38 kV Type VCPW-HD Simple Electrical
Ground & Test Device (SEG&TD) lower
terminal instruction booklet
EATON
www.eaton.com
Figure 48. Shutter secured, locking the test probes in place.
3.6.2.7 Rack the breaker in the cell
3.6.2.7.1 Open the breaker
Key
outside
SEOG&TD
Key captured in
Selector
switch
KK # 1
KK # 2
KK # 3
KK # 4
KK # 5
KU
KB
KC
No key
KD
No key
OPEN
1. Remove key “KD” from Lock #5 and insert key “KD” into Lock
#4. Rotate key “KD” to release key “KB”.
2. Insert key “KB” into Lock #1 and rotate key “KU”. This electri-
cally enables the 38 kV SEG&TD.
3. Turn the selector switch to the “OPEN” position (Figure 7).
4. On the remote operator depress the “Open” button. The
38 kV SEG&TD will open (Figure 49).
5. Return the selector switch to the “OFF” position and unplug the
remote operator (Figure 50).
Figure 49. Depress the “Open” button momentarily on the
remote operator.
3.6.2.7.2 Racking breaker to Connect position
Key
outside
SEOG&TD
Key captured in
Selector
switch
KK # 1
KK # 2
KK # 3
KK # 4
KK # 5
KU
KB
KC
No key
KD
No key
OFF
1. Turn the selector switch to the “OFF” position and unplug the
remote operator.
2. Follow the same procedure as detailed in section 3.3: Steps 1
through 16 for racking the SEG&TD completely at "CONNECT"
position inside the cell.
3. The feeder can be now tested.
3.6.2.8 Probing the voltage:
Key
outside
SEOG&TD
Key captured in
Selector
switch
KK # 1
KK # 2
KK # 3
KK # 4
KK # 5
KU
KB
KC
No key
KD
No key
CLOSE
1. Make sure selector switch is in the “OFF” position.
2. Plug in the remote operator to the receptacle in the front of the
38 kV SEG&TD.
3. Rotate the selector switch to the “Close” position.
4. On the remote operator, depress the “Close” buttons momen-
tarily; the 38 kV SEG&TD will charge and close automatically.
Thus, lower terminals are probed.
3.7 Removing the test probes
3.7.1 Open the breaker
Key
outside
SEOG&TD
Key captured in
Selector
switch
KK # 1
KK # 2
KK # 3
KK # 4
KK # 5
KU
KB
KC
No key
KD
No key
OPEN
1. Make sure the kirk keys follows the key positions as shown in
the table above.
2. Turn the selector switch to the “OPEN” position.
3. On the remote operator depress the “Open” buttons. The 38
kV SEG&TD will open.
4. Return the selector switch to the “OFF” position and unplug the
remote operator.
Figure 50. Selector switch in the “Off” position.