Publication Number AD05006002E
Page 3
Building and Configuring a SmartWire-DT System Offline with
SWD-Assist
SWD-Assist opens in the offline environment with a PROFIBUS-DP® gateway on
the project screen. For this example we are using the Ethernet gateway. On the
left portion of the screen, if it is not already expanded, expand Network
Infrastructure, then Master Modules under it. The screen should look like the
following:
The SmartWire-DT Ethernet gateway is located under Master Modules. The part
number is EU5C-SWD-EIP-MODTCP. Grab, drag and drop it onto the project
screen over the PROFIBUS-DP gateway. It will drop onto the other gateway,
replacing it. Then click the gateway’s icon on the project screen. Then click the
Device Parameter tab below. This is where the Ethernet protocol is selected.
Choose Modbus TCP for this example. Under the Ethernet Parameters tab is
where the EtherNet/IP Address, Subnet Mask and Gateway addresses are
entered. Also, be sure to set the DIP switches on the gateway to represent the
low octet of the IP address for the module. Disable BootP and DHCP to use a
static IP address.
Next drag and drop the SmartWire-DT node devices in the order that they are
listed in the previous section. You may need to expand sections on the left