manualshive.com logo in svg
background image

4

Series NRX drawout and breaker 

three-way cable interlock installation

and removal instructions

EATON 

www.eaton.com

Instructional Leaflet

 IL01301060E

Effective June 2016

Figure 6. Step 6.

Step 7e:

  Before reattaching the cover, the drive arm window must be 

removed from the side of the cover (Figure 7).  Either use a utility knife 

to cut the window from the cover, or use a punch and a small hammer 

to carefully punch out the window.  Once the window is removed, 

use a small file to remove any burrs that remain.  Make certain that all 

pieces and/or particles are cleaned up and removed before proceeding.

Figure 7.  Step 7.

m

 ATTENTION

FIGURE 8 SHOWS THE TYPICAL CABLE ROUTING FOR BOTH TYPES 31 AND 

33 INTERLOCKS AND FIGURE 9 SHOWS THE TYPICAL ROUTING FOR TYPE 

32 INTERLOCKS.  THE CABLE MOUNTING ON THE DRIVE SIDE IS THE SAME 

FOR ALL TYPES.  MOUNTING FOR THE DRIVEN SIDE OF TYPES 31 AND 33 IS 

SHOWN IN FIGURES 14-16.  MOUNTING FOR THE DRIVEN SIDE OF TYPE 32 IS 

SHOWN IN FIGURES 17-20.

Step 8e: 

This step offers cable routing and installation procedures.  

Make sure that cables move freely in their cable housings before 

installation.

(G)

(H)

Remove drive 

arm window

Installation recommendationse:

 

• 4 inch (102 mm) minimum allowable cable housing bend radius

 

• Use plastic wire ties/clamps to attach cable housing to structure 

after installation and adjustment

 

• Do not compress cable housing

 

• Recheck to ensure cables move freely

Figure 8. 

Type 31 cable routing

Type 33 cable routing.

Step 8.

Содержание Series NRX

Страница 1: ...FLET COULD RESULT IN DEATH BODILY INJURY OR PROPERTY DAMAGE m WARNING THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS HAVE TO BE FOLLOWED OBSERVE THE FIVE SAFETY RULES DISCONNECTING ENSURE...

Страница 2: ...ion of the breakers and are available in 5 6 8 and 10 foot lengths 1 5 1 8 2 4 and 3 0 m Individual cable kits are ordered separately Required tools 10 mm socket drive socket 11 16 inch open end wrenc...

Страница 3: ...nted as shown Torque to 65 85 in lbs 7 3 9 6 N m Step 4 Install the trip pin A to the trip arm using an M3 x 16 mm flat head screw B Use a wrench to hold the trip lever during installation Torque to 3...

Страница 4: ...E 8 SHOWS THE TYPICAL CABLE ROUTING FOR BOTH TYPES 31 AND 33 INTERLOCKS AND FIGURE 9 SHOWS THE TYPICAL ROUTING FOR TYPE 32 INTERLOCKS THE CABLE MOUNTING ON THE DRIVE SIDE IS THE SAME FOR ALL TYPES MOU...

Страница 5: ...f bulkhead fitting enters slotted hole in cable bracket threads show above bracket 7 Bring bulkhead washer and nut down to threads and hand tighten 8 Adjust two bulkhead nuts to approximately center b...

Страница 6: ...el fitting Lower nuts Rubber boot Outer bulkhead nut Bulkhead nut Driven end cable bracket Swivel fitting Driven end long rod Lower nuts Driven end cable bracket Figure 15 Step 10 Step 11 This step de...

Страница 7: ...justments on driven long rod end of cable refer to Figure 15 As adjustments are made with the connected breakers in different states of OPEN and CLOSED make certain that gaps between the swivel fittin...

Страница 8: ...mpt 2 CLOSE Breaker C verify Breaker A remains CLOSED Again verify Breaker B will not respond to CLOSE attempt 3 OPEN Breaker A verify Breaker B will not respond to CLOSE attempt 4 OPEN Breaker C all...

Страница 9: ...9 Instruction Leaflet IL01301060E Effective June 2016 Series NRX drawout and breaker three way cable interlock installation and removal instructions EATON www eaton com Notes...

Страница 10: ...riate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A...