![Eaton Series NRX Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/eaton/series-nrx/series-nrx_instruction-leaflet_3721027005.webp)
5
Instruction Leaflet
IL01301060E
Effective June 2016
Series NRX drawout and breaker
three-way cable interlock installation
and removal instructions
EATON
www.eaton.com
Figure 9. Step 8.
Step 9e:
This step describes how to first attach the drive (short rod) end
of a cable to its interlock assembly and cable bracket. See Figures 10
to 14 for details.
1. Remove small nut, compression spring and spacer tube from end
of rod.
2. Slide rubber boot toward tip of rod.
3. Unthread outer bulkhead nut and slide nut and lock washer toward
tip.
4. Insert threaded end of rod into swivel fitting.
5. Slide smaller diameter portion of bulkhead fitting into cable bracket
slot (see Figure 12).
6. Raise cable assembly until threaded portion of bulkhead fitting
enters slotted hole in cable bracket (threads show above bracket).
7. Bring bulkhead washer and nut down to threads and hand tighten.
8. Adjust two bulkhead nuts to approximately center bulk head fitting
on cable mounting bracket.
9. Hand tighten bulkhead nuts only at this time.
10. Slide rubber boot back into place over end of bulkhead fitting.
11. Replace spacer tube, compression spring and small nut on end of
rod.
12. Lower nuts should be shouldered against end of thread and upper
nut tightened against spacer tube (see Figure 13).
13. Hold lower nuts and torque upper nut to 30 - 40 in.-lbs
(3.3 - 4.5 N•m).
Type 32 cable routing
Figure 10. Step 9.
Figure 11.
Rubber boot
Bulkhead nut
Outer
bulkhead nut
Lower nuts
(should be shouldered
against end of thread)
Threaded end
Spacer tube
Compression
spring
Upper nut
Step 9 - Cable assembly (details).
Swivel
fitting
Drive end
cable bracket
Rubber boot
Drive end
(short rod)