22
INM 725B Rev 21
2 .7 AP6 Cell Detail
(Alarm Card - Remote
P
ushbutton)
Cell type
AP6
is used to provide:-
•
Four digital inputs for use with volt-free or powered contacts
•
Six external pushbutton inputs for use with optional remote mounting pushbuttons
as required.
•
Each of the external pushbutton inputs can be programmed to operate as either:- Lamp
Test, Silence, Acknowledge, Reset, 1st Reset or System Test or Sleep Mode as
required. The common return for all remote pushbuttons is +V (+24VDC)
•
The drawing above indicates the standard card types available for cell type AP6.
•
Multiple AP6 cells may be used in applications that require more than 6 x pushbutton
inputs or in systems using multiple pushbutton groups to control selective channels
WARNING !
If remote pushbuttons are used they must be installed in
the same enclosure as the RTK 725B/C annunciator.
ALARM CARD VERSIONS USED IN "AP6" CELLS
(LOWER SLOT)
CB6611POP1 - 24/125V SIGNAL INPUT VERSION
CB6611POP5 - 24/125V SIGNAL INPUT VERSION
PLUS TIME STAMPING OPTION
CB6611POP2 - 48V SIGNAL INPUT VERSION
CB6611POP6 - 48V SIGNAL INPUT VERSION
PLUS TIME STAMPING OPTION
CUSTOMERS
VOLT FREE
INPUTS
3
CHANNEL
2
1
AP6
2C
INPUTS
1C
4
4C
3C
REAR VIEW
PUSHBUTTONS
P2
P1
P4
P3
P6
P5
REMOTE PB CARD VERSIONS USED IN "AP6" CELLS
(UPPER SLOT)
CB9427POP1 – REMOTE PUSHBUTTON