![Eaton RTK 725B range Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/eaton/rtk-725b-range/rtk-725b-range_instruction-manual_526876026.webp)
20
INM 725B Rev 21
2 .5 AP Cell Detail
(
A
larm –
P
ushbutton Cell)
Cell type
AP
is used to provide:-
• Four digital inputs for use with volt-free or powered contacts
• Three external pushbutton inputs for use with optional remote mounting
pushbuttons as required.
• Each of the external pushbutton inputs can be programmed to operate as either:-
Lamp Test, Silence, Acknowledge, Reset, 1st Reset or System Test or Sleep Mode as
required. The common return for all remote pushbuttons is +V (+24VDC)
• The drawing above indicates the standard card types available for cell type AP.
• Multiple AP cells may be used in applications that require more than 3 x pushbutton
inputs or in systems using multiple pushbutton groups to control selective channels
WARNING !
If remote pushbuttons are used they must be installed in
the same enclosure as the RTK 725B/C annunciator.