Eaton - Lighting Systems                                                       iLight Product Series - RI-2    73-897-00     IM8791     Iss 5                   4

8 Analog / digital inputs

Individually programmable as analog or digital 

inputs

Analog input mode:

• 

Suitable for use with rotary and linear 

variable resistors

• 

Reads input voltages from 0 – 10 VDC

• 

Inputs protected for use up to 12 VDC

Digital input mode works with:

Switch closure from the IN to Common 

• 

For use with both momentary and 

maintained inputs

• 

Minimum momentary input pulse 

duration  

20 msec

• 

Switch will see up to 60uA when closed

Open collector NPN active low circuit

• 

On-state voltage ≤ 500mV and capable of 

sinking 60uA

• 

Collector-emitter leakage current ≤ 10 uA

• 

Collector-emitter voltage ≥ supply voltage

Actively driven circuit

• 

Active low voltage ≤ 500mV and  

capable of sinking 60uA

• 

Active high voltage ≥ supply – 1 volt

• 

All analog / digital inputs wire with 2 

part connectors with screw terminals.  

Wire sizes 12 AWG (4mm

2

) to 24 AWG 

(0.25mm

2

).

8 Relay Outputs

• 

Can be wired to provide low voltage or 

line voltage outputs. 

• 

Do not mix low voltage and line voltage 

on relay output terminals

• 

Normally open and Normally closed 

terminals available for each relay

• 

Low voltage volt free outputs 

• 

Line voltage rated at 3 Amps AC for 

general use, resistive, incandescent 

lamps (tungsten), electric discharge 

(ballast) loads and ¼ HP AC motor loads 

for use at 120 VAC.

• 

LED diagnostic indicators for relay status

8 Digital Outputs

• 

LED indication of switched output status

• 

Configurable as digital control channels

• 

Outputs will drive a single LED, or two 

LEDs in a series with up to 20mA of 

current; exact current will depend upon 

the forward voltage drop of the LED used.

• 

Outputs are actively driven high and low 

to TTL voltages with an internal series 

impedance of 220 ohms.

• 

All digital outputs wire with 2 part 

connectors with screw terminals.  Wire 

sizes 12 AWG (4mm

2

) to 24 AWG 

(0.25mm

2

).

Support for multiple control protocols

• 

2 sets of terminals for the iCANnet 

network

• 

RS485 connection to third party devices

• 

DMX 512A output to third party devices

2 Alarm switch inputs

• 

For integration with emergency control 

devices and building management 

systems

• 

For DC use only

• 

Maximum open circuit voltage, 5V

Содержание RI-2

Страница 1: ...RI 2 Relay Interface Installation guide ...

Страница 2: ...91 Iss 5 2 Contents Introduction 3 Weight 3 Dimensions 3 Specification 3 Mounting 5 Supply Wiring 5 iCAN Network Connections 6 Relay Outputs 7 Analog Digital Inputs 7 Digital Outputs 7 RS485 Connections 8 RJ12 Connector 9 Alarm Inputs 9 Service Switches and LEDs 10 ...

Страница 3: ...any 0 10V source can be programmed to control system functions The unit could also be programmed such that system sequences could be activated by a motion detector or other devices on the iCANnetTM network The adaptability and versatility of this product make it an essential item in larger more sophisticated venues where more than just lighting control is required Weight Packed 2 6 kg Unpacked 2 4...

Страница 4: ... voltage outputs Do not mix low voltage and line voltage on relay output terminals Normally open and Normally closed terminals available for each relay Low voltage volt free outputs Line voltage rated at 3 Amps AC for general use resistive incandescent lamps tungsten electric discharge ballast loads and HP AC motor loads for use at 120 VAC LED diagnostic indicators for relay status 8 Digital Outpu...

Страница 5: ...th greater than 50mm is used Mounting Holes The unit is provided with four 1 4in 6mm diameter fixing holes for wall mounting The mounting holes can be accessed by undoing the four screws on the front cover and removing it Supply Wiring Connecting the Supply This unit requires a nominal 240V single phase supply Live Neutral and Earth with 1A capability Keep the supply wiring segregated from the rel...

Страница 6: ...date warranty A maximum segment distance of 3200 ft 1000 m is possible if an additional 12V power supply is used iCAN devices are daisy chained on the network Spurs from the Network are not permitted and will result in communications problems Devices on an iCAN network can be wired in any order Termination is required at both ends of the network NetworkTermination T Indicates where a termination i...

Страница 7: ...h can be configured via software for either digital or analog input signals Individually programmable to be analog or switch inputs Analog inputs accept 0 10VDC signals Note Wire distance from the device to the RI 2 should not exceed 32 feet 10m Connections are made via a 9 way two part connector with screw terminals The unit is supplied with knockouts suitable for 3 4 19mm cable glands for analog...

Страница 8: ...d of the network ensure the appropriate jumper is fitted in the termination ON position as in the following diagram RS485 Connections An RS485 port is provided for connection to third party devices or PC integration The settings are Baud Rate 9600 Baud Data Structure No parity 8 data bits 1 start bit 1 stop bit A removable 4 way connector block is provided for the connection of RS485 Function Alar...

Страница 9: ...tion for the alarm inputs is for all outputs to switch on These inputs are designed for integration with emergency control devices and building management systems using volt free switch inputs The default action for the alarm inputs is for all mapped DMX channels to output 255 digital outputs drive high and relay outputs close They will then remain in this state regardless of any other command rec...

Страница 10: ...on the network The LEDs indicate the following Normal operation Steady green LED blinking 1 x per second Red LED off Message transmission and receipt indicated by red LED flashing for duration of data transmission Override status Both LEDs flashing together or just red flashing and green off ICANnet error status will occur when a Source Controller is not connected to an iCAN network for any reason...

Страница 11: ...tput s should this be suspected When the Source Controller is placed into override mode it will no longer respond to commands sent over the iLight network Override mode can also be used to restore power to outputs if control is lost or termporarly removed to allow lighting to remain on until control is restored NOTE Override mode only affects the outputs on the Source Controller on which it is act...

Страница 12: ...ITY AND THE IMPLIED WARRANTY OF FITNESS No employee agent dealer or other person is authorised to give any warranties on behalf of the Seller or to assume for the Seller any other liability in connection with any of its goods except in writing and signed by the Seller The Seller makes no representation that the goods comply with any present or future federal state or local regulation or ordinance ...

Отзывы: