![Eaton RI-2 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/eaton/ri-2/ri-2_installation-manual_526676006.webp)
Eaton - Lighting Systems iLight Product Series - RI-2 73-897-00 IM8791 Iss 5 6
iCAN Network Connections
Two removable 5 way connector blocks are
provided for the connection of iCAN network
cables. The iCAN terminals on the board are
connected in parallel.wiring. An appropriate
cable gland should be fitted to each knockout
hole to protect the cabling from damage.
IMPORTANT NOTE: Connecting a mains
potential cable to the iLight Network terminals
is likley to damage the unit and others
connected, and invalidate warranty.
* A maximum segment distance of 3200 ft.
(1000 m) is possible if an additional 12V power
supply is used.
iCAN devices are ‘daisy-chained’ on the
network. Spurs from the Network are not
permitted and will result in communications
problems. Devices on an iCAN network can be
wired in any order. Termination is required at
both ends of the network.
Network Termination
T - Indicates where a termination is required.
The RI-2 has built-in network termination. If the
RI-2 is at the end of the network, ensure the
CAN TERM jumper is fitted in the Termination
On position.
Function Belden
1502
CAT5/6
Colour
0V
Black
Green pair
CAN L
White
Blue
Shield
Silver
Brown pair
CAN H
Blue
Blue/white
+12Vdc
Red
Orange pair
Содержание RI-2