Intelligent Technologies (
IT.
) QSNAP
Pub. No. MN05001001E
11
February 2002
Input/Output Data
The QSNAP offers a standard data list (shown below) for default operation. The list is
configurable with data contained within
Table 21
in
Appendix A: QSNAP Parameters
, using
the CH Studio application.
Input Data
Use
Tables 10
and
11
when setting up the QSNAP input data.
Table 10: Input Assembly Data Definitions
Data
Description
Faulted/Trip
The motor controller is faulted or tripped
Warning
The motor controller has a warning of an impending trip
Running 1
The first motor controller is running
Running 2
The second motor controller is running
Permissive
The motor controller run/stop permissive
Resetting
Motor controller is in the process of resetting a fault
Thermal Capacity
% thermal capacity of the motor from 0 to 100%
RMS Average
Current
Average RMS current of the motor (0.000A)
Fault Codes and
Warning Codes
Valid fault and warning codes are:
0
No Fault
1
General Fault
2
Firmware Fault
3
Interdevice Communication Fault
4
Control Voltage Low Fault
5
Control Device Overtemperature Fault
6
Motor Phase Loss Fault
7
Motor Phase Imbalance Fault
8
Motor Ground Fault
9
Motor Underload Fault
10
Motor Overcurrent Fault
13
Motor Bypass Failure Fault
14
Motor Thermal Pile Fault
15
Control Device Test Fault
40000
Current Threshold Warning
40001
Underload Warning
40002
Control Device Overtemperature Warning
40003
Overload Warning