PXG 900 User's Guide - Firmware Version 4.3 - 1/9/2017
25
BACnet IP Server
Setting up a BACnet/IP Server
Note: Edit must be active to make these changes. The Base ID setting won't be reflected in the Device
Mapping
until you save and exit edit mode.
If you enable BACnet/IP. you can present the connected devices as virtual devices on a BACnet/IP virtual network.
Routed Network Number
You must provide the Routed Network Number that will be assigned to the virtual network. Possible values are 1
through 65534. Ask someone in your facility maintenance group that is responsible for maintaining the BACnet
network infrastructure for guidance in selecting a Routed Network Number. The Routed Network Number must be
unique from all other BACnet network numbers within the BACnet global network.
Caution: If you choose a Routed Network Number that is already in use, communications problems
will result.
Base ID for Auto-Assign
This is the base ID value used by auto-assign (if enabled) to assign the gateway and virtual device instance
numbers.
Auto-Assign Gateway ID
If enabled, the ID for the gateway is automatically assigned. If you set a Base ID, the gateway will be the base value
plus one. If disabled, you can manually set the ID by clicking View Map.
Auto-Assign Device IDs
The various virtual device IDs will be assigned based on the Base ID (if specified) and incrementing from the ID
assigned to the gateway. If disabled, you can manually set the IDs by clicking View Map.
BACnet Broadcast Management Device
If you're using a BACnet Broadcast Management Device (BBMD) to connect your meter to another subnet in your
BACnet/IP network, you must also define the BBMD IP address (IPV4 only) to register with the BBMD on the remote
subnet. You can also set the BBMD Time to Live value in seconds.
Содержание PXG 900
Страница 1: ...PXG 900 User s Guide Power Xpert Gateway 900 ...
Страница 14: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 12 Adding an IQ 250 ...
Страница 16: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 14 Adding a Digitrip 1150 ...
Страница 18: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 16 Adding a BIM II ...
Страница 21: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 19 Locale Settings ...
Страница 40: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 38 Audit Logs ...
Страница 45: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 43 Alarm level field for multi state channels ...
Страница 53: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 51 Device Details ...