80 kVA - 130 kVA UPS
User’s and Installation Manual
1017397
Revision D (update)
44
3. Electrical characteristics / Input
3.1 Nominal voltage
220/380, 230/400, 240/415 V; 50/60 Hz
3.2 Fluctuation
342 to 456 V; 45 to 65 Hz
3.3 Current
80 kVA:
3 x 102 A (-N / -NHS)
3 x 120 A (-SCRF)
3 x 147 A (-SCR)
100 kVA: 3 x 127 A (-N / -NHS)
3 x 153 A (-SCRF)
3 x 181 A (-SCR)
130 kVA: 3 x 165 A/ (-N / -NHS)
3 x 200 A (-SCRF)
3 x 230 A (-SCR)
3.4 Power factor / THD
0.99 / 3% (-N / -NHS)
0.84 / 15% (-SCRF)
0.73 / 30% (-SCR)
4. Electrical characteristics / Output
4.1 Nominal power
80 kVA / 100 kVA / 130 kVA at PF 0.8
4.2 Nominal voltage
220/380, 230/400, 240/415; 50/60 Hz
4.3 Crest factor
3:1 computer and server loads
4.4 Linear loads
0.8 lagging to 0.9 leading
4.5 Voltage regulation
±1% at static, ±5% at dynamic operation;
4.6 Current
80 kVA:
3 x 116 A
100 kVA: 3 x 145 A
130 kVA: 3 x 188 A
4.7 Short circuit capability
520 Amp phase to neutral,
- max 300 ms duration
300 Amp phase to phase or limited by the
bypass line impedance and fusing.
4.8 Voltage distortion (VHD)
Max. 3% with linear loads;
Max. 5% with non linear loads
4.9 Syncronisation to bypass input
±0.5, ±1.0, ±1.5, ±2.0, ±2.5 or ±3 Hz with
slew rate of changes <0.5 Hz per second;
±0,05 Hz free running.
4.10 Parallel load sharing
±5% of the rated load
- Hot Sync
®
models only (-NHS)