15
User Manual
MN040024EN
Effective November 2016
DX-NET-ETHERNET2-2 fi eld bus connection
EtherNet/IP for variable frequency drive DE1/DC1
EATON
www.eaton.com
Input data words
DE1/DC1 command
Setpoint value
The permissible values fall within a range of P1-02 (minimum frequency) to P1-01 (maximum frequency).
This value will be scaled with a factor of 0.1 in the application.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
Process data input 3 (PDI3) – not used
The value is not used.
Process data input 4 (PDI 4) – acceleration time
The permissible value fall within a range of the drives 0 to 300 sec on DE1 and 0 to 600 sec on DC1 ,
refer to setting of P-03. Value is scaled with a factor of 0.01 in the application. This input is only active
when P-12 is set to a value of 4 in DC1.