4 Commissioning
4.8 Parameter
46
DX-NET-DEVICENET
02/14 MN04012005ZEN
www.eaton.com
4.8 Parameter
The abbreviations used in the parameter lists below have the following
meaning:
Figure 17:How the parameters are shown in the manual and in the software
The Baud rate will automatically be set to match the master.
4.8.0.1 Acyclic Parameters
The module can be used to read and program parameters.
Access to the DA1 variable frequency drive‘s acyclic data is provided by
object class A2h. The relevant ADI number can be found in
PNU
Parameter number
ID
Identification number of the parameter
RUN
Access rights to the parameters during operation (RUN):
/ = Modification permissible
- = Modification only possible in STOP
ro | rw
Parameter read and write permissions via a fieldbus connection:
ro = read only
rw = read and write (read and write)
Value
Setting of the parameter
DS
Default setting: (P1.1 = 1) base parameter
→
Access rights are not shown in the drivesConnect PC software.
Manual
PNU
ID
Access right
Value
Description
DS
RUN
ro | rw
①
②
③
④
PC Software
PNU
Description
Value
Range
Default
Visible
①
③
②
④
PNU
ID
Access right
Designation
Value range
DS
Value that must
be configured
RUN
ro | rw
P1-12
112
–
rw
Control level
0 = Control signal terminals (I/O)
1 = Keypad (KEYPAD FWD)
2 = Keypad (KEYPAD FWD/REV)
3 = PID control
4 = field bus system (PROFINET-2, Modbus RTU, etc.)
5 = Slave mode
6 = field bus CANopen
0
4