Step 5—Standard Parameter List
16
PowerXL DG1 Series Adjustable Frequency Drives
MN040012EN—March 2014
www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P3.15
2
Accel/Decel Time Set
0
195
See P3.2
P3.16
2
Accel/Decel Prohibit
0
201
See P3.2
P3.17
2
No Access To Param
0
215
See P3.2
P3.21
2
Remote Control
9
196
See P3.2
P3.22
2
Local Control
0
197
See P3.2
P3.23
2
Remote1/2 Select
0
209
See P3.2
P3.26
2
DC Brake Enable
0
202
See P3.2
P3.32
2
Jog Enable
0
199
See P3.2
P3.36
2
AI Ref Source Select
0
208
See P3.2
P3.42
2
Emergency Stop
8
747
See P3.2
Table 12. Analog Output—P4
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P4.1
2
AO1 Mode
0
227
0 = 0–20 mA
1 = 0–10V
P4.2
2
AO1 Function
1
146
0 = Not Used
1 = Output Frequency
2 = Freq Reference
3 = Motor Speed
4 = Motor Current
5 = Motor Torque (0–Nom)
6 = Motor Power
7 = Motor Voltage
8 = DC-Bus Voltage
19 = AI1
20 = AI2
21 = Output Freq (–2 to +2N)
22 = Motor Torque (–2 to +2N)
23 = Motor Power (–2 to +2N)
24 = PT100 Temperature
P4.3
2
AO1 Minimum
1
149
0 = 0V / 0 mA
1 = 2V / 4 mA
P4.4
2
AO1 Filter Time
0.00
10.00
s
1.00
147
P4.5
2
AO1 Scale
10
1000
%
100
150
P4.6
2
AO1 Inversion
0
148
See P2.6
P4.7
2
AO1 Offset
–100.00
100.00
%
0.00
173
P4.8
2
AO2 Mode
0
228
See P4.1
P4.9
2
AO2 Function
4
229
See P4.2
P4.10
2
AO2 Minimum
1
232
See P4.3
P4.11
2
AO2 Filter Time
0.00
10.00
s
1.00
230
P4.12
2
AO2 Scale
10
1000
%
100
233
P4.13
2
AO2 Inversion
0
231
See P2.6
P4.14
2
AO2 Offset
–100.00
100.00
%
0.00
234
Table 11. Digital Input—P3, continued
Code
Parameter
Min.
Max.
Unit
Default
ID
Note