7 Serial interface (Modbus RTU)
7.2 Modbus parameters
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
143
7.2 Modbus parameters
The following table 16 shows the Modbus parameters in the DC1 frequency
inverter.
RUN
Indicates the access right during operation (FWD or REV)
- = No parameter change possible,
/
= Parameter change possible.
ro/rw
Indicates the access right via the field bus
ro = Read only possible,
rw = Read and write possible.
Table 16:
Modbus parameters
PNU
ID
Access rights
Designation
Value range
DS
RUN
ro/rw
P-36
164
–
rw
Frequency inverter slave
address
0 - 63
1
rw
Baud rate
1 = OP-buS
2 = 9.6 kBit/s
3 = 19.2 kBit/s
4 = 38.4 kBit/s
5 = 57.6 kBit/s
6 = 115.2 kBit/s
OP-buS
rw
TimedOut
0 - 3000 ms
3000 ms
P-12
140
–
rw
Control level
0 = Control signal terminals (I/O)
1 = Keypad (KEYPAD FWD)
2 = Keypad (KEYPAD FWD/REV)
3 = Modbus, with internal acceleration and deceleration ramp
4 = Modbus, acceleration and deceleration ramps via bus
5 = PI controller with external actual value
6 = PI controller with external actual value and totalized value of
AI1
7 = CANopen, with internal acceleration and deceleration ramp
8 = CANopen, acceleration and deceleration ramps via bus
0
Содержание PowerXL DC1
Страница 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 32: ...1 DC1 device series 1 12 Service and warranty 28 DC1 frequency inverter 10 12 MN04020003Z EN www eaton com...
Страница 52: ...2 Engineering 2 5 Motor and Application 48 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...