6 Parameters
6.3 Operational data indicator
136
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
6.3 Operational data indicator
When the specified supply voltage is applied (L1/L, L2/N, L3), the 7-segment
LED display will be illuminated (Power ON); the display will show “Stop“.
You can use arrow buttons
▲
and
▼
to select the operational data indicator
you want (parameter number P00-…) in the “Monitor“ (P-00…) menu. You
can tell the display to stop alternating between the parameter number and
the display value and only show the display value instead by pressing the OK
button. If you want to access a different operational data indicator, press the
OK button again. You can then make your selection using the
▲
and
▼
arrow
buttons and confirm it with the OK button.
→
The values of the operating data display cannot be changed by
hand (i. e. by value entry).
PNU
ID
Access rights
Value
Description
DS
RUN
ro/rw
P-01
129
✓
rw
Maximum frequency / maximum speed
50.0
P-10 = 0
→
P-02 - 5 x P-09
→
Hz
P-10 > 0
→
P02 - 5 x P-09 x 60 s
→
min-1
The maximum output frequency / motor speed limit – shown in Hz or rpm
(if P-10 > 0).
P-02
130
✓
rw
Minimum frequency / minimum speed
0
P-10 = 0
→
0 - P-01
→
Hz
P-10 > 0
→
0 - P01
→
min-1
The minimum output frequency / minimum speed – shown in Hz or rpm (if
P-10 > 0).
P-03
131
✓
rw
Acceleration time (acc1)
5
0.1 - 600 s (
P-04
132
✓
rw
Deceleration time (dec1)
5
0.1 - 600 s (
P-05
133
✓
rw
Stop Function
1
0
Ramp, deceleration = dynamic braking
Deceleration time with the value set under P-04 (dec1).
If the energy that is fed back by the motor during dynamic braking is too
high, the deceleration time must be increased.
In devices with an internal braking transistor, the excess energy can be
dissipated with an external braking resistor (optional) (
6.2.11.2, „Regenerative braking“, page132).
1
Free coasting
After the start enable (FWD/REV) is switched off or the STOP pushbutton
is pressed (P-12 and P-15), the motor will coast uncontrolled.
2
Ramp, quick stop = dynamic braking
Deceleration time 2 with the value set under P-24 (dec2)
If the energy that is fed back by the motor during dynamic braking is too
high, the deceleration time must be increased.
In devices with an internal braking transistor, the excess energy can be
dissipated with an external braking resistor (optional) (
Содержание PowerXL DC1
Страница 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 32: ...1 DC1 device series 1 12 Service and warranty 28 DC1 frequency inverter 10 12 MN04020003Z EN www eaton com...
Страница 52: ...2 Engineering 2 5 Motor and Application 48 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...