6 Parameters
100
DC1 Frequency Inverter
10/12 MN04020003Z-EN
www.eaton.com
P-32
160
✓
rw
0 - 25 s
DC-braking
0
Used to define the length of time during which direct current will be
applied to the motor if the output frequency reaches a value of 0.0 Hz.
Note:
The voltage level will be the same as the voltage amplification set in
P-11.
P-33
161
✓
rw
Motor pick-up control function (to catch spinning motors) (in sizes FS2
and FS3) / DC braking, braking time at start (in size FS1)
0
If this parameter is enabled, the frequency inverter will attempt to
determine whether the motor is already turning during a start. It will
then start to control the motor starting from the motor's current speed.
A brief deceleration will occur if motors that are not already turning are
started.
Note:
Direct current connection time when starting (FS1-size frequency
inverters only): Used to set the length of time during which a direct
current will be applied to the motor in order to ensure that it will be
stopped if the frequency inverter is activated.
0
Deactivated
1
activated
P-34
162
✓
rw
Brake chopper activation (only with sizes FS2 and FS3)
0
0
locked
1
Enabled with overload protection braking resistance
2
Enabled without overload protection braking resistance
P-35
163
✓
rw
Analog input 1 scaling
100
0 - 500 %
Used to scale the analog input by this factor.
Example: For P-16 and a 0 -10 V signal and a scaling factor of 200.0 %,
a 5 V input will make the frequency inverter run at the maximum
frequency / speed (P-01).
P-36
164
–
rw
Serial communication configuration
This parameter has three settings that are used to configure serial
Modbus RTU communications.
These subparameters are as follows:
0 - 63
Frequency inverter slave address
1
Baud rate
OP-buS
1
OP-buS
2
9.6 kBit/s
3
19.2 Kbit/s
4
38.4 kBit/s
5
57.6 kBit/s
6
115.2 kBit/s
TimedOut
3000 ms
locked, 30 - 3000 ms
PNU
ID
Access rights
Value
Description
DS
RUN
ro/rw
Содержание PowerXL DC1
Страница 1: ...Manual PowerXL DC1 Frequency Inverter 10 12 MN04020003Z EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Units 8 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 32: ...1 DC1 device series 1 12 Service and warranty 28 DC1 frequency inverter 10 12 MN04020003Z EN www eaton com...
Страница 52: ...2 Engineering 2 5 Motor and Application 48 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...
Страница 190: ...9 Appendix 9 9 Sinusoidal filter 186 DC1 Frequency Inverter 10 12 MN04020003Z EN www eaton com...