MBM INSTALLATION PLAN AND UNPACKING
Eaton 9395 Maintenance Bypass Module Installation and Operation Manual
S
164201719 Rev 3
www.eaton.com/powerquality
3-9
Table 3‐7. Input/Output Ratings and External Wiring Requirements for the
Eaton 9395 550 kVA MBM with Five Wire Bypass Input
Basic Unit Rating
Units
UPS Rating 50/60 Hz
kVA
450
500
550
Input and Output Voltage
Volts
480/480
480/480
480/480
AC Input to Maintenance Bypass with or
without Optional BIB
(dual-feed UPS)
(3) Phases, (1) Neutral, (1) Ground
A
Amps
541
601
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
250
(3)
300
(3)
300
(4)
AC Input to Maintenance Bypass with
Optional BIB
(single-feed UPS)
(3) Phases, (1) Neutral, (1) Ground
A
Amps
600
660
740
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
250
(3)
300
(3)
300
(4)
AC Input to Maintenance Bypass with
Optional BIB and RIB
(dual-feed UPS)
(3) Phases, (1) Neutral, (1) Ground
A
Amps
600
660
740
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
250
(3)
300
(3)
300
(4)
AC Output from Optional RIB to UPS
(3) Phases, (1) Ground
B
Amps
600
660
740
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
4/0
(3)
350
(3)
350
(3)
AC Output from Optional BIB to UPS
(3) Phases, (1) Neutral, (1) Ground
C
Amps
541
601
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
250
(3)
300
(3)
300
(4)
AC Input from UPS to MIS
(3) Phases, (1) Neutral, (1) Ground
D
Amps
541
601
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
250
(3)
300
(3)
300
(4)
AC Output to Critical Load
(3) Phases, (1) Neutral, (1) Ground
E
Amps
541
601
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
250
(3)
300
(3)
300
(4)
NOTE
Callout letters
A
,
B
,
C
,
D
and
E
map to Figure 5‐3 on page 5-5, Figure 5‐4 on page 5-6, Figure 5‐5