MBM INSTALLATION PLAN AND UNPACKING
Eaton 9395 Maintenance Bypass Module Installation and Operation Manual
S
164201719 Rev 3
www.eaton.com/powerquality
3-6
For external wiring requirements, including the minimum AWG size of external wiring,
see Table 3‐4 and Table 3‐5 for the 9395 275 kVA MBM or Table 3‐6 and Table 3‐7 for
the 9395 550 kVA MBM.
Table 3‐4. Input/Output Ratings and External Wiring Requirements for the
Eaton 9395 275 kVA MBM with Four Wire Bypass Input
Basic Unit Rating
Units
UPS Rating 50/60 Hz
kVA
225
275
Input and Output Voltage
Volts
480/480
480/480
AC Input to Maintenance Bypass with or without
Optional BIB
(dual-feed UPS)
(3) Phases, (1) Ground
A
Amps
271
331
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
AC Input to Maintenance Bypass with Optional BIB
(single-feed UPS)
(3) Phases, (1) Ground
A
Amps
300
370
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
AC Input to Maintenance Bypass with Optional
BIB and RIB
(dual-feed UPS)
(3) Phases, (1) Ground
A
Amps
300
370
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
AC Output from Optional RIB to UPS
(3) Phases, (1) Ground
B
Amps
300
370
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
AC Output from Optional BIB to UPS
(3) Phases, (1) Ground
C
Amps
271
331
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
AC Input from UPS to MIS
(3) Phases, (1) Ground
D
Amps
271
331
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
AC Output to Critical Load
(3) Phases, (1) Ground
E
Amps
271
331
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
NOTE
Callout letters
A
,
B
,
C
,
D
and
E
map to Figure 5‐3 on page 5-5, Figure 5‐4 on page 5-6, Figure 5‐5