EATON
Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide
S
164201378 Rev C
www.power-
ware.com
21
Chapter 3
EBM Maintenance
This section explains how to:
S
Care for the UPS and batteries
S
Replace the Extended Battery Modules (EBMs)
S
Recycle used batteries or UPS
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS
clean and dust-free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
NOTE
The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the batteries every
6 months by plugging the UPS into a power outlet. The batteries charge
to 90% capacity in approximately 3 hours. However, it is recommended
that the batteries charge for 24 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date
has expired and the batteries were never recharged, do not use the
UPS. Contact your service representative.
When to Replace Batteries
When the
indicator flashes and the audible alarm beeps once every
five seconds, the batteries may need replacing. Contact your service
representative to order new batteries.