INSTALLATION
EATON
Powerware
®
5125 Two-in-One EBM (2400/3000 VA) User’s Guide
S
164201378 Rev C
www.power-
ware.com
20
9.
Verify that all battery circuit breakers are in the OFF (O) position
(see Figure 10).
10.
Plug the EBM cable(s) into the battery connector(s) as shown in
Figure 10. Up to four EBMs may be connected to the UPS.
11.
Follow the installation instructions in the
Powerware 5125
Two-in-One UPS (2500/3000 VA) User’s Guide
for installing the
UPS.
NOTE
The batteries charge to 90% capacity in approximately 3 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long-term storage.
NOTE
Ensure maximum battery runtime by using the ERM configuration tool on the
Software Suite CD.
NOTE
If more than two EBMs are installed, an external battery charger is recommended
for faster recharge times.
UPS Battery
Connector
EBM Battery
Connectors
Joining Brackets
EBM Cables
ON
OFF
Battery Circuit Breaker
UPS
EBM
EBM
Figure 10. Tower EBM Connections (120V Model Shown)