UPS MAINTENANCE
Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide
S
164201449 Rev B
www.eaton.com/powerquality
50
4.
Pull the battery group out onto a flat, stable surface. See “Recycling
the Used Battery or UPS” on page 51 for proper disposal.
Figure 28. Removing the Battery
5.
Slide the new battery group into the UPS.
6.
Reinstall the battery cover removed in Step 3.
7.
Reconnect the internal battery connector.
8.
Replace the UPS front cover.
Testing New Batteries
NOTE
The batteries must be fully charged and the UPS must not be in Battery mode to
perform the self‐test.
Press and hold the
button for three seconds to initiate a self-test.
The 15-second test automatically distributes the load to the batteries
and tests the battery's performance. While the test is in progress, the
indicators cycle through and the alarm sounds. When complete, the UPS
returns to Normal mode as indicated by the
and Load indicators.
If there is a problem with the battery, the alarm beeps, the
+ -
indicator
illuminates and the
indicator flashes. Check the battery connections
and be sure the battery is fully charged. Call your service representative
if the problem persists.