48
9. Modbus register map
Power XPert® release triP unit for MagnuM PXr circuit breakers
MN013015EN January 2022 www.eaton.com
Table 30. Modbus event registers (continued).
function
code
register
number
address
(hex)
format
Definition
3, 4
8227
0x2022
Unsigned32
IG residual
3, 4
8229
0x2024
Unsigned16
VAB
3, 4
8230
0x2025
Unsigned16
VBC
3, 4
8231
0x2026
Unsigned16
VCA
3, 4
8232
0x2027
Unsigned16
VAN
3, 4
8233
0x2028
Unsigned16
VBN
3, 4
8234
0x2029
Unsigned16
VCN
3, 4
8235
0x202A
Signed32
Real 3-phase power (W)
3, 4
8237
0x202C
Signed32
Reactive 3-phase power (VAR)
3, 4
8239
0x202E
Unsigned32
Apparent 3-phase power (VA)
3, 4
8241
0x2030
Signed32
Real 3-phase power demand (W)
3, 4
8243
0x2032
Signed32
Reactive 3-phase power demand (VAR)
3, 4
8245
0x2034
Unsigned32
Apparent 3-phase power demand (VA)
3, 4
8247
0x2036
Singed16
Device temperature (1/10 °C)
3, 4
8248
0x2037
Unsigned16
Frequency (1/10 Hz)
3, 4
8249
0x2038
Singed16
Apparent power factor (1/100 pf)
3, 4
8250
0x2039
Unsigned16
Operations count
3, 4
8251
0x203A
Bits
Binary status with validity bits
trip or major alarm