42
9. Modbus register map
Power XPert® release triP unit for MagnuM PXr circuit breakers
MN013015EN January 2022 www.eaton.com
Table 24. Modbus system group data (continued).
func.
code
register
number
address
(hex)
setpoint name
r/w
Definition
3,4,6
3015
0x0BC6
Relay #1 configuration
R/W
Relays support maximum of 2 mappings. 1
st
mapping in the low
byte, 2
nd
mapping in the high byte.
0 = OFF
1 = overload trip
2 = neutral trip
3 = short delay trip
4 = short circuit trip
5 = instantaneous trip
6 = ground fault trip
7 = maintenance mode trip
8 = all trips
9 = high load alarm 1
10 = high load alarm 2
11 = high temperature
12 = ground fault
13 = thermal memory
14 = watchdog
15 = low battery
16 = internal fault
17 = setpoint mismatch
18 = low health
19 = communication fault
20 = all faults
21 = aux contact
22 = bell contact
23 = maintenance mode active
24 = ZSI active
25 = ZSI input
26 = ZSI output
27 = open breaker pulse
28 = close breaker pulse
29 = remote control
3,4,6
3016
0x0BC7
Relay #2 Configuration
R/W
Same as Relay #1
3,4,6
3017
0x0BC8
Relay #3 Configuration
R/W
Same as Relay #1