38
9. Modbus register map
Power XPert® release triP unit for MagnuM PXr circuit breakers
MN013015EN January 2022 www.eaton.com
Table 20. Modbus real-time data (continued).
func.
code
register number address (hex)
Description
units
scale
factor
ieee
float
integer
ieee
float
integer
3,4,6
5025
6561
0x13A0 0x19A0
Write one of the following values to
this register to select the harmonics
of interest (default=0):
0 - Ia
1 - Ib
2 - Ic
4 - In
5 - Vab
6 - Vbc
7 - Vca
8 - Van
9 - Vbn
10 - Vcn
3,4
5027
6563
0x13A2 0x19A2
Harmonic content 1st
%
100
3,4
5029
6565
0x13A4 0x19A4
Harmonic content 2nd
%
100
3,4
5031
6567
0x13A6 0x19A6
Harmonic content 3rd
%
100
3,4
…
…
…
…
Harmonic content …
%
100
3,4
5087
6623
0x13E0 0x19E0
Harmonic content 31st
%
100
9.3.1
Status within the real-time data register
Register Number 6145 and 6146 provide status information
about the breaker according to Table 20.