47
9. Modbus register map
Power XPert® release triP unit for MagnuM PXr circuit breakers
MN013015EN January 2022 www.eaton.com
Table 30. Modbus event registers (continued).
function
code
register
number
address
(hex)
format
Definition
3, 4, 6, 16
8193
0x2000
Encoded
Event type: event = 0x8EFF
3, 4
8194
0x2001
Unsigned32
Earliest event ID
3, 4
8196
0x2003
Unsigned32
Latest event ID
3, 4, 16
8198
0x2005
Unsigned32
Requested event ID
3, 4
8200
0x2007
Unsigned32
Previous event ID
3, 4
8202
0x2009
Unsigned32
Next event ID
3, 4
8204
0x200B
Date/Time
Date/time
3, 4
8212
0x2013
Encoded
Format of data: 0x0000, 0x0001, 0x0004, 0x0005, 0x0006
3, 4
8213
0x2014
B0
Object validity bits
3, 4
8214
0x2015
Encoded
Event cause:
00 = power up – time OK
01 = setpoints download
02 = time adjusted
03 = trip
04 = alarm
05 = enter test mode
06 = exit test mode
08 = power up - no time
09 = test completed
10 = maintenance mode active
11 = maintenance mode inactive
12 = opened by communications
13 = closed by communications
Minor alarm
function
code
register
number
address
(hex)
format
Definition
3, 4, 6, 16
8193
0x2000
Encoded
Event type: alarm = 0x81FF
3, 4
8194
0x2001
Unsigned32
Earliest event ID
3, 4
8196
0x2003
Unsigned32
Latest event ID
3, 4, 16
8198
0x2005
Unsigned32
Requested event ID
3, 4
8200
0x2007
Unsigned32
Previous event ID
3, 4
8202
0x2009
Unsigned32
Next event ID
3, 4
8204
0x200B
Date/time
Date/time
3, 4
8212
0x2013
Encoded
Format of data: minor alarm 0x0006
3, 4
8213
0x2014
Bits
Object validity bits
3, 4
8214
0x2015
Encoded
Status cause (primary, secondary, cause)
trip or major alarm
function
code
register
number
address
(hex)
format
Definition
3, 4, 6, 16
8193
0x2000
Encoded
Event type: trip = 0x80FF, alarm = 0x81FF
3, 4
8194
0x2001
Unsigned32
Earliest event ID
3, 4
8196
0x2003
Unsigned32
Latest event ID
3, 4, 16
8198
0x2005
Unsigned32
Requested event ID
3, 4
8200
0x2007
Unsigned32
Previous event ID
3, 4
8202
0x2009
Unsigned32
Next event ID
3, 4
8204
0x200B
Date/time
Date/time
3, 4
8212
0x2013
Encoded
Format of data: trip = 0x0004, major alarm 0x0005
3, 4
8213
0x2014
Bits
Object validity bits
3, 4
8214
0x2015
Bits
Object validity bits
3, 4
8215
0x2016
Encoded
Status cause (primary, secondary, cause)
3, 4
8217
0x2018
Unsigned32
IA
3, 4
8219
0x201A
Unsigned32
IB
3, 4
8221
0x201C
Unsigned32
IC
3, 4
8223
0x201E
Unsigned32
IN
3, 4
8225
0x2020
Unsigned32
IG source
sumary events
.