UPS INSTALLATION PLAN AND UNPACKING
Eaton
Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual
S
P-164000563 Rev 1
www.eaton.com/powerquality
3-11
Terminals E1 through E11 are 2‐hole busbar mountings for standard NEMA 2‐hole
barrel lugs. The power wiring connections for this equipment are rated at 90
°
C. See
Table 3‐8 for supplied terminal hardware, and Table 3‐9 for recommended installation
parts and tools not supplied by Eaton.
Table 3‐8. Supplied External Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Bolt, Grade 5
M10 x 30 mm
12
Ground and Neutral
180190078-088
Bolt, Grade 5
M12 x 45 mm
26
Rectifier Input, Bypass Input,
Battery Input, and Output
180190078-113
Flat Washer
M10
12
Ground and Neutral
180500036-100
Flat Washer
M12
52
Rectifier Input, Bypass Input,
Battery Input, and Output
180500036-120
Conical Washer
M10
12
Ground and Neutral
180500037-100
Conical Washer
M12
26
Rectifier Input, Bypass Input,
Battery Input, and Output
180500037-120
Nut
M12
26
Rectifier Input, Bypass Input,
Battery Input, and Output
180200001-07
NOTE
Bypass terminations are not applicable to IOM configurations.
Table 3‐9. Recommended Installation Parts and Tools (Not Supplied by Eaton
)
Part
Size
Quantity
Manufacturer
Part Number
Notes
Long Barrel 2‐Hole Lug
2/0 AWG
As required
Thomas & Betts
54862BE
Copper wire only
3/0 AWG
Thomas & Betts
54864BE
4/0 AWG
Thomas & Betts
54866BE
250 MCM
Thomas & Betts
54868BE
300 MCM
Thomas & Betts
54870BE
350 MCM
Thomas & Betts
54872BE
400 MCM
Thomas & Betts
54874BE
500 MCM
Thomas & Betts
54876BE
Manual Hydraulic Crimp Tool
14 Ton
1
Thomas & Betts
TBM14M
Die Set
N/A
1
Thomas & Betts
15506
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See
Table 3‐10 for conduit requirements.
Per NEC article 300, 3(B)(1), all three‐phase conductors must be run in the same
conduit.
Conduit is sized to accommodate one neutral conductor the same size as the phase
conductor and one ground conductor sized in accordance with NEC Table 250.122.