P-164000476
9395P 500kVA / 600 kVA
116
Revision 002
User’s and Installation Guide
5.
Close all UPS Bypass input feeder circuit breakers.
6.
Close the doors and secure the latches.
7.
Observe the UPS control panel displays becoming active, indicating logic power.
8.
On any UPS, press the LOCK icon on the main screen. The Sign In screen is displayed. Use
operator password to log in (factory default password is 0101).
9.
Select CONTROLS on the main screen. SYSTEM CONTROLS screen opens up.
10. Select GO TO BYPASS. Command confirmation pop-up screen will show up asking confirmation for
the action. Select YES.
The critical load is immediately supplied by the bypass source in Bypass mode from all UPSs.
The BYPASS status indicator is illuminated. The UPS status is On Bypass. The UPM status is
shutdown.
7.5.3 Enable Variable Module Management System mode from the EEA
controls menu
For instructions, see Section 7.4.5 “Enable Variable Module Management System mode from the EEA
controls menu” on page 106.
7.5.4 Disable Variable Module Management System mode from the EEA
controls menu
For instructions, see Section 7.4.6 “Disable Variable Module Management System mode from the EEA
controls menu” on page 107.
7.5.5 How to start High Alert Timer from the EAA Controls menu
For instructions, see Section 7.4.7 “Start Variable Module Management System High Alert mode from
the EEA controls menu” on page 107.
7.5.6 Starting the UPS UPMs
To start the power modules without transferring the critical load to Normal mode:
1
Unfasten the front door latches and swing the doors open on all of the UPSs.
2.
If the UPSs contain input breakers (CB1), verify that all input breakers are open.
3.
Close all UPS input feeder circuit breakers.
4.
If the UPSs contain input breakers (CB1), close all input breakers.
5.
Close all UPS Bypass input feeder circuit breakers.
6.
Close the doors and secure the latches.
7.
Observe the UPS control panel displays becoming active, indicating logic power.
8.
On any UPS, press the LOCK icon on the main screen. The Sign In screen is displayed. Use
operator password to log in (factory default password is 0101).
9.
Select CONTROLS on the main screen. SYSTEM CONTROLS screen is displayed.
10. Select MODULE CONTROLS. All the installed UPMs and their status can be seen here.
11. On the MODULE CONTROLS screen, select UPM1.
12. Select START UPM to start UPM1. Command confirmation pop-up screen shows up asking
confirmation for the action. Select YES.
13. The UPM1 rectifier and inverter will turn on and the UPM goes to IDLE state. The UPS status
changes to READY. The UPS is ready to transfer to the Normal mode and supply the critical load.
14. Repeat steps 10 through 12 by choosing another UPM until all the UPMs are in IDLE state.
15. Repeat steps 8 through 14 for each UPS in the distributed bypass system.
Содержание Power Xpert 9395P
Страница 1: ...User s and Installation Guide Power Xpert 9395P UPS 500 kVA 600 kVA P 164000476 ...
Страница 2: ...P 164000476 9395P 500kVA 600 kVA 2 Revision 002 User s and Installation Guide ...
Страница 18: ...P 164000476 9395P 500kVA 600 kVA 8 Revision 002 User s and Installation Guide ...
Страница 37: ...P 164000476 9395P 500kVA 600 kVA 27 Revision 002 User s and Installation Guide ...