P-164000476
9395P 500kVA / 600 kVA
107
Revision 002
User’s and Installation Guide
4.
Select ENABLE VMMS. Command confirmation pop-up screen will show up asking confirmation
for the action. Select YES.
5.
The UPS transfers to Variable Module Management System mode. In approximately twenty
seconds the UPS calculates the required number of UPMs needed to support the load. The Online
status indicator is illuminated. The UPS status indicates VMMS. The UPM status
indicates active or idle.
7.4.6 Disable Variable Module Management System mode from the EEA
controls menu
To disable Variable Module Management System mode:
NOTE
The Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually
exclusive. If the Energy Saver System mode is enabled, the Variable Module Management
System mode commands will not be displayed.
1
Press the LOCK icon on the main screen. The Sign In screen is displayed. Use operator password
to log in (factory default password is 0101).
2.
Select CONTROLS on the main screen. SYSTEM CONTROLS screen opens up.
3.
Select EAA CONTROLS. This screen shows if VMMS is installed or not.
4.
Select DISABLE VMMS. Command confirmation pop-up screen will show up asking confirmation
for the action. Select YES.
5.
The UPS transfers to Battery mode and then to Normal mode in approximately ten seconds. The
Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates
active.
7.4.7 Start Variable Module Management System High Alert mode from
the EEA controls menu
To start High Alert mode:
NOTE
The High Alert mode commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually
exclusive. If the Energy Saver System mode is enabled, the Variable Module Management
System mode commands will not be displayed.
1
Press the LOCK icon on the main screen. The Sign In screen is displayed. Use operator password
to log in (factory default password is 0101).
2.
Select CONTROLS on the main screen. SYSTEM CONTROLS screen opens up.
3.
Select EAA CONTROLS.
4.
Select START HIGH ALERT TIMER. Command confirmation pop-up screen will show up asking
confirmation for the action. Select YES.
Содержание Power Xpert 9395P
Страница 1: ...User s and Installation Guide Power Xpert 9395P UPS 500 kVA 600 kVA P 164000476 ...
Страница 2: ...P 164000476 9395P 500kVA 600 kVA 2 Revision 002 User s and Installation Guide ...
Страница 18: ...P 164000476 9395P 500kVA 600 kVA 8 Revision 002 User s and Installation Guide ...
Страница 37: ...P 164000476 9395P 500kVA 600 kVA 27 Revision 002 User s and Installation Guide ...