P-164000476
9395P 500kVA / 600 kVA
106
Revision 002
User’s and Installation Guide
13. The UPM1 rectifier and inverter will turn on and the UPM goes to IDLE state. The UPS status
changes to READY. The UPS is ready to transfer to the Normal mode and supply the critical load.
14. Repeat steps 10 through 12 by choosing another UPM until all the UPMs are in IDLE state.
NOTE
To transfer to Normal mode after starting individual UPMs, follow the procedure in Section 7.4.9.
7.4.4 Starting a single UPM
To start a single UPM:
1
Unfasten the front door latch and swing the door open.
2.
If the UPS contains input breaker CB1, verify that input breaker CB1 is open.
3.
Close the UPS input feeder circuit breaker.
4.
Close the UPS Bypass input feeder circuit breaker.
5.
If the UPS contains input breaker CB1, close input breaker CB1.
6.
Close the door and secure the latch.
7.
Observe the UPS control panel becoming active, indicating logic power.
8.
Close the battery breaker.
9.
Press the LOCK icon on the main screen. The Sign In screen is displayed. Use operator password
to log in (factory default password is 0101).
10. Select CONTROLS on the main screen. SYSTEM CONTROLS screen is displayed.
11. Select MODULE CONTROLS. All the installed UPMs and their status can be seen here.
12. On the MODULE CONTROLS screen, select the desired UPM.
13. Select GO TO NORMAL to transfer the UPM to normal mode. Command confirmation pop-up
screen will show up asking confirmation for the action. Select YES.
If Auto Bypass is enabled (factory default), the critical load is immediately supplied by the bypass
source, in Bypass mode, until the inverter turns on and the UPS transfers to Online mode. The status
indicator on the UPS control panel indicates the UPS is in Bypass mode. If Auto Bypass is not enabled,
the UPS output remains off until the UPS transfers to Online mode.
7.4.5 Enable Variable Module Management System mode from the EEA
controls menu
To enable Variable Module Management System mode:
NOTE
The Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually
exclusive. If the Energy Saver System mode is enabled, the Variable Module Management
System mode commands will not be displayed.
1
Press the LOCK icon on the main screen. The Sign In screen is displayed. Use operator password
to log in (factory default password is 0101).
2.
Select CONTROLS on the main screen. SYSTEM CONTROLS screen opens up.
3.
Select EAA CONTROLS. This screen shows if VMMS is installed or not.
Содержание Power Xpert 9395P
Страница 1: ...User s and Installation Guide Power Xpert 9395P UPS 500 kVA 600 kVA P 164000476 ...
Страница 2: ...P 164000476 9395P 500kVA 600 kVA 2 Revision 002 User s and Installation Guide ...
Страница 18: ...P 164000476 9395P 500kVA 600 kVA 8 Revision 002 User s and Installation Guide ...
Страница 37: ...P 164000476 9395P 500kVA 600 kVA 27 Revision 002 User s and Installation Guide ...