FIELD INSTALLED UPM INSTALLATION
Power Xpert
9395P Field Installed UPM Mechanical Installation Manual
S
P-164000503 Rev 1
4-2
NOTE
For the following steps, verify that the forklift or pallet jack is rated to handle the weight of the
cabinet (see Table 3‐1 on page 3-2 for cabinet weight).
1.
If not already accomplished, use a forklift or pallet jack to move the cabinet to the
installation area, or as close as possible, before unloading from the pallet. If
possible, move the cabinet using the pallet. Insert the forklift or pallet jack forks
from the right side of the pallet (facing the cabinet), between the supports on the
bottom of the pallet (see Figure 3‐6 on page 3-6 for the FI-UPM cabinet center of
gravity measurements).
2.
Remove the three bolts securing the left side shipping bracket to the cabinet and
three bolts securing the bracket to the pallet (see Figure 4‐1). Remove the left
side shipping bracket. If installing the cabinet permanently, retain the shipping
bracket and securing hardware for later use.
Shipping Bracket
Bolts
Shipping Bracket
Bolts
Pallet
Left Side Shipping
Bracket
FI-UPM Removable
Front Panel
Figure 4‐1. Removing the Left Side Shipping Bracket
3.
Remove the three bolts securing the right side shipping bracket to the cabinet
and three bolts securing the bracket to the pallet (see Figure 4‐2). Remove the
right side shipping bracket.
4.
Using a forklift, raise the FI-UPM cabinet section until the cabinet bottom clears
the pallet by approximately 3 mm (1/8
”
).
5.
Pull the pallet from under the FI-UPM cabinet.