26
Eaton PDI JCOMM Enclosure Installation and Operation Manual P-164001107—Rev 01
Figure 17. Network Segmentation When a Monitor is Present
When planning BCMS with local JCOMM monitors, plan for remapping panelboard and subdistribution feed
Modbus addresses to the monitor’s upstream side. These remapped addresses are what the BMS must use to
address the downstream BCMS devices (
).
Figure 18. Modbus Upstream Address Remapping with JCOMM Monitor
If you use SNMP as the protocol upstream from the monitor, the monitor does not remap Modbus addresses,
because there is only one Modbus network segment and only one client.