Eaton PDI JCOMM Enclosure Installation and Operation Manual P-164001107—Rev 01
Table 7. BCMS Measurements: Normal and Power-KWH Points Lists
BCMS Measurements: Normal and Power-KWH Points Lists
BC = branch circuit, PB = panelboard
Direct Measurements
Current, branch circuits 1-42
Direct measurement from branch circuit CTs
Current, main feeds ABCNG
Specify which main circuit phases are monitored with CTs in setup. If there are
no main feed CTs, BCMS computes main feed ABC values for each panelboard
from branch circuit current totals. (Note: this computed value is not a simple
sum of BC measurements.)
Voltage source 1 and voltage source 2
Voltage source 1 is required. JCOMM BCMS can monitor two voltage sources.
Voltage is measured at one source per panelboard.
Frequency
Frequency is measured from voltage source 1 or 2, phase A.
Accumulated and Derived Data – Branch Circuits
Minimum current (BC 1-42)
The lowest current measured on each branch circuit
Maximum current (BC 1-42)
The highest current measured on each branch circuit
KW (BC 1-42)
The
Power-KWH points list
provides detailed power measurements for each
branch circuit as shown in this section (grey background).
These measurements are not available in the
Normal
points list.
KVA (BC 1-42)
KVAR (BC 1-42)
Power Factor (BC 1-42)
Accumulated and Derived Data – Panelboards
Current, ABC, each panelboard
PB total current is measured from main feed CTs or computed by BCMS from
branch circuit current measurements.
Current, ABC, panelboards summed
Current for both PBs summed is measured from a single main feed to both PBs
or a computed sum of the current to both PBs. (Not available if panelboards
use separate voltages)
Percent total load on panelboard
Full load
on a panelboard is specified during setup. BCMS reports panelboard
usage as a percentage of
full load
, but does not use this number as an alarm.
Real Power kW
PB power measurement
Real Power phase A
PB power measurement
Real Power phase B
PB power measurement
Real Power phase C
PB power measurement
Reactive Power kVAR
PB power measurement
Apparent Power kVA
PB power measurement
Total Power Factor phase A
PB power measurement
Power Factor phase A
PB power measurement
Power Factor phase B
PB power measurement
Содержание PDI JCOMM
Страница 1: ...p n P 164001107 Revision 01 Installation and Operation Manual Eaton PDI JCOMM Enclosure...
Страница 4: ......
Страница 8: ...viii Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 List of Figures...
Страница 10: ...x Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 List of Tables...
Страница 12: ...2 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Safety...
Страница 44: ...34 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Operation...
Страница 46: ...36 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Service...
Страница 48: ...38 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Bibliography...
Страница 50: ...P 16400110701 P 164001107 01...