EATON
Installation & Maintenance Instructions
TM396 – XF-XP-XT LW UL ISS.A
4 |
P a g e
1.0 General
Important Safeguards and Warnings
This symbol indicates that there are important operating and maintenance instructions in the literature
accompanying this unit. Prior to installation and use of this product, observe the following warnings.
1.
Installation and servicing should only be carried out by qualified service personnel and in
accordance with all local/national codes of practice and standards e.g. UL1203 Edn.5, NFPA 70 - no
modification to the certified product allowed.
2.
It is essential that provision is made for overload, short circuit and earth fault protection for this
equipment. Therefore, we recommend that a double pole, mains rated, miniature circuit breaker
rated to the max power consumption of the unit, must be incorporated in the electrical installation
of the power supply to this product.
3.
A readily accessible disconnection device shall be incorporated in the electrical installation wiring,
to provide all pole isolation of the supply to the equipment.
4.
Only use tools and replacement parts supplied or recommended by EATON. This unit does not
contain any user serviceable parts.
5.
Care must be taken to ensure selection of suitable cables connecting to these units, when installed
in operating temperatures above +70°C.
6.
The equipment is designed to satisfy the requirements of UL60065 7
th
Edition 2013/07/24. CSA
C22.2 No. 60065-03 2012/08/01 Safety Requirements ANNEX II of ATEX directive 94/9/EC.
7.
Be aware that aggressive substances may require extra protection of the equipment to maintain its
integrity and explosion protection.
8.
The equipment may need additional means of protection if it is to be installed in locations where it
may be exposed to excessive external stresses e.g. vibration, heat, impact and damage.
9.
Any repairs or replacement parts must be done by the manufacturer or an approved repair agent.
10.
Due to the weight of the units, correct planning and equipment must be used when unpacking and
installing. When handling the XP and XT units, the correct lifting points must be adhered to (see
section 3.1.2 for safe lifting points.)
11.
For systems fitted with integral Fiber Optic transmitters, the fiber optic cabling used has additional
protective measures to ensure that the optical radiation is confined within the cabling, by the use
of a robust conduit covering externally, and Kevlar braided cable inside the conduit and the
enclosure. NFPA 70 500.8 (F)
12.
When batteries are fitted to electronic equipment they must be removed and are not to be
replaced.
13.
After installation, operatives must adhere to the following warning on the unit’s label:
WARNING: DO NOT OPEN WHEN ENERGISED OR WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT. CLEAN WITH DAMP CLOTH
This symbol indicates that dangerous voltage constituting a risk of electric shock may be present within this
unit
.