Table 3-3: Group 2 — Operation Method Parameters
Table 3-4: Group 3 — Output Function Parameters
Code
Parameter
Min.
Max.
Unit
Default
Cust
Note
2-00
Source of frequency
command
0
4
0
0:
Digital keypad
1:
0 – 10V from AVI
2:
4 – 20 mA from AVI
3:
Controlled by V.R. on drive
4:
RS-485 communication interface
2-01
Source of operation
command
0
4
0
0:
By digital keypad
1:
By external terminals, keypad
STOP enable
2:
By external terminals, keypad
STOP disable
3:
By RS-485 communication
interface, keypad STOP enable
4:
By RS-485 communication
interface, keypad STOP disable
2-02
Stop method
0
1
0
0:
Ramp stop
1:
Coast stop
2-03
Carrier frequency
3
10K
Hz
10
3 – 10K Hz
2-04
Reverse operation
inhibit
0
2
0
0:
Enable reverse
1:
Disable reverse
2:
Disable forward
2-05
ACI (4 – 20 mA) input
loss detection
0
2
0
0:
Decelerate to 0 Hz
1:
Stop immediately, display EF
2:
Run with the last frequency
2-06
Line start lockout
0
1
0
0:
Enable
1:
Disable
Code
Parameter
Min.
Max.
Unit
Default
Cust
Note
3-00
Desired frequency
attained
1.0
400
Hz
1.0
1.0 – 400 Hz
3-01
Terminal count value
0
999
0
0 – 999
3-02
Preliminary count
value
0
999
0
0 – 999
3-03
Multi-function relay
output
0
16
8
0:
Not used
1:
AC drive operational
2:
Maximum output frequency
attained
3:
Zero speed
4:
Over torque
5:
Base-block (B.B.)
6:
Low voltage detection
7:
AC drive operation mode
8:
Fault indication
9:
Desired frequency attained
10:
PLC program running
11:
PLC program step complete
12:
PLC program complete
13:
PLC program operation pause
14:
Terminal count value attained
15:
Preliminary count value attained
16:
Ready state indicator