Table B-1: Communication Address Definition, continued
Content:
Address:
Function:
(Reserved)
2101H,
continued
Bit 5
Not used
Bit 5-7
Not used
Bit 8
1: Main freq. controlled by communication
Bit 9
1: Main freq. controlled by external terminal
Bit 10
1: Operation command controlled by communication
Bit 11
1: Parameters been locked
Bit 12-15
Not used
2102H
Frequency command. (FXXX.XX)
2103H
Output frequency. (HXXX.XX)
2104H
Output current. (AXX.X)
2105H
DC-BUS voltage. (UXXX)
2106H
Output voltage. (EXXX)
2107H
Step number of multi-step speed operation.
2108H
Step number of PLC operation.
2109H
Time of PLC operation.
210AH
Value of the counter.